Item | 1625A Class 20 Olr W/ Everlink Power Ter |
Width | 55 mm |
Height | 70 mm |
Depth | 123 mm |
Standards | EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495 |
Thermal Overload Class | class 20 IEC 60947-4-1 |
Associated Fuse Rating | 4 A gG signalling circuit || 4 A BS signalling circuit |
Connections - Terminals | control circuit screw clamp terminals 2 1-2.5 mm? flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm? flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm? solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm? flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm? flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm? solid without cable end |
Auxiliary Contact Composition | 1 NO + 1 NC |
Device Short Name | LRD |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
Temperature Compensation | -20-60°C |
Mounting Support | plate, with specific accessories || rail, with specific accessories || under contactor |
Flame Retardance | V1 conforming to UL 94 |
Phase Failure Sensitivity | tripping current 130 % of Ir on two phase, the last one at 0 |
[Ui] Rated Insulation Voltage | power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1 |
Network Frequency | 0 to 400 Hz |
Network Type | AC || DC |
Ambient Air Temperature For Operation | -20-60°C without derating IEC 60947-4-1 |
Product Certifications | IEC || UL || CSA || CCC || EAC || DNV-GL || RMRS || EU-RO MR || LROS (Lloyds register of shipping) || ATEX INERIS || UKCA |
Mechanical Robustness | shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations4 gn IEC 60068-2-6 |
Ambient Air Temperature For Storage | -60-70°C |
Climatic Withstand | IACS E10 |
Product Compatibility | LC1D40A || LC1D65A || LC1D50A |
Product Or Component Type | differential thermal overload relay |
[Ue] Rated Operational Voltage | 690 V AC 0 to 400 Hz power circuit IEC 60947-4-1 |
Product Name | TeSys LRD || TeSys Deca |
Range | TeSys || TeSys Deca |
Thermal Protection Adjustment Range | 17-25 A |
[Ith] Conventional Free Air Thermal Current | 5 A signalling circuit |
Tripping Threshold | 1.14 +/- 0.06 Ir IEC 60947-4-1 |
Tightening Torque | control circuit 1.7 N.m screw clamp terminals || power circuit 5 N.m EverLink BTR screw connectors |
Permissible Current | 3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit |
Control Type | Red push-button stop || Blue push-button reset |
Dielectric Strength | 1.89 kV 50 Hz IEC 60947-1 |
Ip Degree Of Protection | IP20 conforming to IEC 60529 |
Relay Application | motor protection |
Country of Origin (subject to change) | France |
Package Quantity | 1 |