Temp. Rating
194 Degrees F
Nominal Outside Dia.
0.44 in
Insulation Material (Wire and Cable)
PVC
Wire Type - Wire and Cable
THHN
Insulation Material - Wire and Cable
PVC
Packaging
Wood Reel with Fiber Drum
Wire Size - Wire and Cable
1 AWG
Jacket Material - Wire and Cable
Nylon
Wire and Cable Item
Building Wire
Wire Size (Wire and Cable)
1 AWG
Application
Wet or Dry Locations (Below 90°C), Locations Exposed to Oil (Below 75°C)
Length (Straight Wireway)
500 ft
Allowable Ampacity At 90C
145
Jacket Thickness (Mils)
8mils
Insulation Thickness (Mils)
50mils
Allowable Ampacity At 60C
110
Construction
ConstructionSouthwire® SIMpull THHN® copper conductors are made with soft drawn copper. Combination-unilay stranding. The wire is covered with a tough heat and moisture resistant PVC insulation with an overall nylon jacket utilizing SIMpull® Technology. Marked as THWN-2. Marked sunlight resistant.
Applications
ApplicationSouthwire® SIMpull THHN® copper conductors are primarily used in conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications as specified in the National Electrical Code. Voltage for all applications is 600 volts. SIMpull THHN® copper conductors are designed to be installed without application of a pulling lubricant.THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75° C when exposed to oil
Allowable Ampacity At 75C
130
Country of Origin (subject to change)
United States