Full Load Amps-Inductive | 80 A |
Item | IEC Magnetic Contactor |
Full Load Amps-Resistive | 125 A |
Action | Non-Reversing |
Number of Poles | 3 |
Coil Volts | 240 V AC |
Reversing | No |
HP @ 1 Phase - 120V | 7 1/2 hp |
HP @ 1 Phase - 230V | 15 |
HP @ 1 Phase - 240V | 15 hp |
Height | 5 in |
Width | 3.34 in |
HP @ 3 Phase - 208V | 30 hp |
HP @ 3 Phase - 575V | 60 hp |
HP @ 3 Phase - 240V | 30 hp |
Depth | 5.12 in |
HP @ 3 Phase - 480V | 60 hp |
Enclosure NEMA Rating | No Enclosure |
Aux. Contact Configuration | 1NO/1NC |
Hz | 50/60 |
Frame / Series / Class / Code | TeSys |
Standards | BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UL 508, UL Listed |
Auxiliary Contact Form | 1NO/1NC |
NEMA Size | Not Applicable |
Series | TeSys Deca |
Signalling Circuit Frequency | 25 to 400 Hz |
Features | Without Built-In Suppressor Module |
Mounts On | Plate, Rail |
Mechanical Durability | 4 Mcycles |
Insulation Resistance Range | Greater Than 10 MOhms (Signalling Circuit) |
Operating Time | 20 to 35 ms (Closing), 6 to 20 ms (Opening) |
Includes Protective Cover | Yes |
Shock Resistance | 10 G for 11 ms (Contactor Closed), 8 G for 11 ms (Contactor Open) |
Fuse Amps | 10 A (Signalling Circuit), 200 A (Type 1 Power Circuit), 160 A (Type 2 Power Circuit) |
Impulse Withstand Voltage | 8 kV |
Operating Speed | 3600 cycles per hr |
Rated Insulation Volts | 600/1000V (Power Circuit), 600/690V (Signalling Circuit) |
Vibration Resistance | 3 G (Contactor Closed), 2 G (Contactor Open) |
Impedance | 0.8 mOhm |
Watts Loss | 6 to 10W |
Thermal Amperage | 10 A (at 60°C Signalling Circuit), 125 A (at 60°C Power Circuit) |
Inrush VA | 245 VA |
Electrical Connection | Screw Clamp Terminals |
Non-Overlap Time | 1.5 ms |
Application | Motor Control, Resistive Load |
Environmental Attributes | Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3 |
Tightening Torque | 1.2 Nm (Control Circuit), 12 Nm (Power Circuit) |
Net Weight | 1.59 kg |
Max. Operating Watts | 22 kW (at 220 to 230V AC 50/60 Hz AC-3), 37 kW (at 380 to 400V AC 50/60 Hz AC-3), 45 kW (at 415 to 440V AC 50/60 Hz AC-3), 55 kW (at 500V AC 50/60 Hz AC-3), 45 kW (at 660 to 690V AC 50/60 Hz AC-3), 15 kW (at 400V AC 50/60 Hz AC-4), 22 kW (at 220 to 230V AC 50/60 Hz AC-3e), 37 kW (at 380 to 400V AC 50/60 Hz AC-3e), 45 kW (at 415 to 440V AC 50/60 Hz AC-3e), 55 kW (at 500V AC 50/60 Hz AC-3e), 45 kW (at 660 to 690V AC 50/60 Hz AC-3e) |
Fire Rating | UL 94 V1 |
Electrical Durability | 0.8 Mcycles (125 A, AC-1, Less than 440 V), 1.5 Mcycles (80 A, AC-3, Less than 440 V), 1.5 Mcycles (80 A, AC-3e, Less than 440 V) |
Rated Voltage | 690V AC, 300V DC |
Overvoltage Category | CAT III |
Switching Current | 5 mA (Signalling Circuit) |
Rated Breaking Capacity | 1100 A @ 440V |
Rated Short-Time Withstand Current | 640 A (at 40°C for 10 s Power Circuit), 990 A (at 40°C for 1 s Power Circuit), 135 A (at 40°C for 10 min Power Circuit), 320 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit) |
Max. Temperature | 850°C |
IP Rating | IP20 |
Switching Voltage | 17 V (Signalling Circuit) |
Hold VA | 26 VA |
Control Circuit Voltage Limits | Operational AC: 0.85 to 1.1 Uc (at -40 to 55°C 60 Hz), 0.8 to 1.1 Uc (at -40 to 55°C 50 Hz), 1 to 1.1 Uc (at 55 to 70°C 50/60 Hz), Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz) |
Working Height | Up to 9842.52 ft |
Rated Making Capacity | 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1100 A @ 440V (Power Circuit) |
Embedded Surge Suppressor | No |
Minimum Operating Temperature | -40 Degrees F |
Number of Normally Open Main Contacts | 3 |
Mounting Style | DIN Rail, Plate |
Overall Height | 5 in |
Horsepower @ Three Phase - 240V AC | 30 hp |
Frequency | 50/60 Hz |
Maximum Voltage Rating | 300V DC |
Overall Width | 3.35 in |
Mechanical Operating Durability | 4,000,000 |
Full Load Current - Inductive | 80 A |
Horsepower @ Single Phase - 240V AC | 15 hp |
Coil Voltage | 240V AC |
Horsepower @ Three Phase - 480V AC | 60 hp |
Overall Depth | 5.12 in |
Full Load Current - Resistive | 125 A |
Reversing Capability | Non-Reversing |
Horsepower @ Single Phase - 120V AC | 7 1/2 hp |
Electrical Operating Durability | 1,500,000, 800,000 |
Number of Auxillary Contacts | 2 |
NEMA Enclosure Material | Not Applicable |
Terminal Connection Type | Screw Clamp Terminals |
Includes Auxiliary Contacts | Yes |
Maximum Operating Temperature | 140 Degrees F |
Horsepower @ Three Phase - 208V AC | 30 hp |
Horsepower @ Three Phase - 600V AC | 60 hp |
Contactor Style | IEC |
Resistance Properties | Fire Resistant, Insulation Resistant |
Phase | Three |
NEMA Enclosure Rating | No Enclosure |
Country of Origin (subject to change) | Czechia |
Package Quantity | 1 |
IEC Magnetic Contactor, 3 Poles, 240 V AC, 80 A, Reversing: No, SCHNEIDER ELECTRIC, Mfr# LC1D80U7
$388.96
Free shipping will be applied on orders over $50
IEC Magnetic Contactor, Auxiliary Contact Form 1NO/1NC, NEMA Enclosure Rating No Enclosure, NEMA Size Not Applicable, Coil Voltage 240V AC, Number of Poles 3, Full Load Current - Inductive 80 A, Full Load Current - Resistive 125 A, Reversing Capability Non-Reversing, Overall Height 5 in, Overall Width 3.35 in, Terminal Connection Type Screw Clamp Terminals, Mounting Style DIN Rail, Plate, Series TeSys Deca, Number of Auxillary Contacts 2, Contactor Style IEC
9999 in stock
Must order in multiples of 1
Subtotal:
$388.96
You must be logged in to post a review.
Reviews
There are no reviews yet.