Standards
EU RoHS, UL listed file E2875
Includes
Dual Cover Interlock
Neutral Assembly Included
Yes
Maximum Enclosure Depth
7.04 in
Fuse Kit (Class R)
Mfr. No. RFK10
Mounting Style
Surface Mount
Features
Quick Make/Break Operating Mechanism, Viewing Window
Number of Mounting Holes
4
Includes Interlocked Receptacle
Yes
For Fuse Class
Class H, Class K
Horsepower @ 480V AC
Not Rated
Compatible with Manufacturer Model Number
RFK10
Horsepower @ 600V AC
Not Rated
Compatible with Manufacturer Model Number [NEW]
RFK10
Compatible Manufacturer Part Number
RFK10
Compatible Manufacturer Model Number
RFK10
For Use with Mfr. Model Number
RFK10
For Use With Mfr. Model Number
RFK10
Device Application
heavy application
Tightening Torque
50-50 lbf.in (AWG 1...AWG 3/0) || 45-45 lbf.in (AWG 6...AWG 4) || 40-40 lbf.in 8.367-8.367 mm² (AWG 8) || 35-35 lbf.in 2.06-5.261 mm² (AWG 14...AWG 10)
Electrical Connection
lugs
Product Or Component Type
Single Throw Safety Switch
Wiring Configuration
4-wire (3PH + N)
[Ue] Rated Operational Voltage
250 V DC || 240 V AC
Condition Of Use
suitable service entrancefor USA || suitable service entrancefor Mexico
Device Composition
neutral (factory installed)
Disconnector Device Type
fusible disconnect
Fuse Type
H or K || R or J
Awg Gauge
AWG 12...AWG 1/0 aluminium || AWG 14...AWG 1/0 copper
Product Certifications
UL listed file E2875
Nema Degree Of Protection
NEMA 1 steel
Short-Circuit Current
10 kA for H, K, J or R without fuse rejection clips || 200 kA for R with fuse rejection clips || 200 kA for J
Country of Origin (subject to change)
United States