Item | Auxiliary Contact Block |
Number of NO Aux. Contacts | 3 |
Number of NC Aux. Contacts | 1 |
Amps | 10 A |
Mounting | Front |
For Use With | Schenider LC1F Contactors |
Number of Contacts | 4 |
Max. Contact Blocks (No.) | 1 |
Voltage | 690V AC |
Color | Dark Gray |
Depth | 42 mm |
Standards | EN/IEC 60947-5-1, UL 60947-5-1, CSA C22.2 No 60947-5-1, GB/T 14048.5, CB, CCC, EAC, UKCA |
Height | 48 mm |
Width | 44 mm |
Features | Mercury Free, Toxic Heavy Metal Free |
Compatible with Series | TeSys, TeSys Deca, TeSys F |
Terminal Connection Type | Screw Clamp Terminals |
Maximum Voltage Rating | 690V AC |
Number of Normally Closed Contacts | 1 |
IP Rating | IP22 |
Current AC | 10 A |
Number of Normally Open Contacts | 3 |
Permissible Short-Time Rating | 100 A 140°F (60°C) 1 s, 120 A 140°F (60°C) 500 ms, 140 A 140°F (60°C) 100 ms |
Range Compatibility | TeSys D CAD, TeSys D LC1D, TeSys F LC1F, TeSys F CR1F, TeSys Deca CAD, TeSys Deca LC1D |
Rated Insulation Voltage | 690 V IEC 60947-5-1, 600 V UL, 600 V CSA |
Ambient Air Temperature For Storage | -76 to 176°F (-60 to 80°C) |
Product Name | TeSys Deca |
Tightening Torque | 15.05 lbf.in (1.7 N.m) flat 6 mm, 15.05 lbf.in (1.7 N.m) Philips No 2, 15.05 lbf.in (1.7 N.m) pozidriv No 2 |
Conventional Free Air Thermal Current | 10 A (at 140°F (60°C)) |
Rated Operational Voltage | 690 V AC 25 to 400 Hz |
Pole Contact Composition | 3 NO + 1 NC |
IP Degree Of Protection | IP2X conforming to IEC 60529 |
Non-Overlap Time | 1.5 ms on de-energisation no overlap between NC and NO contact, 1.5 ms on energisation no overlap between NC and NO contact |
Connections - Terminals | screw clamp terminals 1 0.00 to 0.01 in? (1 to 4 mm?)flexible with cable end, screw clamp terminals 1 0.00 to 0.01 in? (1 to 4 mm?)flexible without cable end, screw clamp terminals 2 0.00 to 0.00 in? (1 to 2.5 mm?)flexible with cable end, screw clamp terminals 2 0.00 to 0.01 in? (1 to 4 mm?)flexible without cable end, screw clamp terminals 1 0.00 to 0.01 in? (1 to 4 mm?)rigid without cable end, screw clamp terminals 2 0.00 to 0.01 in? (1 to 4 mm?)rigid without cable end |
Product Certifications | CB, UL, CSA, CCC, EAC, UKCA |
Rated Operational Current | 6 A at 120 V AC-15, 1.04 A at 690 V AC-15, 0.55 A at 125 V DC-13, 0.1 A at 600 V DC-13 |
Protective Treatment | TH IEC 60068 |
Insulation Resistance | Greater than 10 MOhm |
Ambient Air Temperature For Operation | 23 to 140°F (-5 to 60°C) |
Contacts Operation | Instantaneous |
IRMS Rated Making Capacity | 140 A AC conforming to IEC 60947-5-1, 250 A DC conforming to IEC 60947-5-1 |
Minimum Switching Voltage | 17 V |
Operating Altitude | 9842.52 ft (3000 m) |
Minimum Switching Current | 5 mA |
Protection Type | GG fuse 10 A |
Mechanical Durability | 30 Mcycles |
Environmental Characteristic | Normal environment |
Country of Origin (subject to change) | France |
Package Quantity | 1 |
IEC Auxiliary Contact, SCHNEIDER ELECTRIC, Mfr# LADN31
$52.53
Free shipping will be applied on orders over $50
Auxiliary Contact Block, Current AC 10 A, Number of Contacts 4, Mounting Front, Number of Normally Open Contacts 3, Maximum Voltage Rating 690V AC, Number of Normally Closed Contacts 1, Terminal Connection Type Screw Clamp Terminals, Compatible with Series TeSys, TeSys Deca, TeSys F, IP Rating IP22
9999 in stock
Must order in multiples of 1
Subtotal:
$52.53
You must be logged in to post a review.
Reviews
There are no reviews yet.