Enclosure NEMA Rating
No Enclosure
Overload Relay Amp Setting
13 to 18A
HP @ 3 Phase - 460-575V
10
Description/Special Features
Melting Alloy Thermal Overload, Single Unit
Phase Loss Sensitivity
Yes
Standards
ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed
Thermal Protection Adjustment Range
13-18 A IEC 60947-4-1
Motor Power Kw
7.5-7.5 kW 400/415 V AC 50/60 Hz || 9-9 kW 500 V AC 50/60 Hz || 15-15 kW 690 V AC 50/60 Hz
Product Or Component Type
motor circuit breaker
Trip Unit Technology
thermal-magnetic
Power Dissipation Per Pole
2.5 W
Phase Failure Sensitivity
yes IEC 60947-4-1
[Ith] Conventional Free Air Thermal Current
18 A IEC 60947-4-1
[Ui] Rated Insulation Voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-2
Mechanical Robustness
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Ip Degree Of Protection
IP20 IEC 60529
Mechanical Durability
100000 cycles
Network Frequency
50/60 Hz IEC 60947-4-1
Fixing Mode
35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
Tightening Torque
1.7 N.m screw clamp terminal
Ambient Air Temperature For Operation
-20-60°C
[Ics] Rated Service Short-Circuit Breaking Capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 50 % 400/415 V AC 50/60 Hz IEC 60947-2 || 50 % 440 V AC 50/60 Hz IEC 60947-2 || 75 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
Ik Degree Of Protection
IK04
Rated Duty
continuous IEC 60947-4-1
Ambient Air Temperature For Storage
-40-80°C
Electrical Durability
100000 cycles AC-3 415 V In
Device Application
motor protection
Product Certifications
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
Breaking Capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 8 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Utilisation Category
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Climatic Withstand
IACS E10
Operating Altitude
6561.68 ft (2000 m)
Suitability For Isolation
yes IEC 60947-1§ 7-1-6
Magnetic Tripping Current
223-223 A
Fire Resistance
960°C IEC 60695-2-11
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Product Name
TeSys GV2 || TeSys Deca
Minimum Overload Relay Current Setting
13 A
Status Indicator
No Indicator
Resistance Properties
Fire Resistant
Maximum Voltage Rating
690V AC
Minimum Operating Temperature
-4 Degrees F
Horsepower @ Single Phase - 120V AC
1 hp
Horsepower @ Three Phase - 208V AC
5 hp
Maximum Overload Relay Current Setting
18 A
Horsepower @ Single Phase - 240V AC
3 hp
Mechanical Operating Durability
100,000
Horsepower @ Three Phase - 240V AC
3 hp
Electrical Operating Durability
100,000
Horsepower @ Three Phase - 480V AC
10 hp
Horsepower @ Three Phase - 600V AC
10 hp
Overload Protection Type
Thermal
NEMA Enclosure Rating
No Enclosure
Maximum Operating Temperature
140 Degrees F
Terminal Connection Type
Screw Clamp Terminals
Rated Service Short-Circuit Breaking Capacity
100% 230/240 V AC 50/60 Hz IEC 60947-2; 50% 400/415 V AC 50/60 Hz IEC 60947-2; 50% 440 V AC 50/60 Hz IEC 60947-2; 75% 500 V AC 50/60 Hz IEC 60947-2; 75% 690 V AC 50/60 Hz IEC 60947-2
Country of Origin (subject to change)
Thailand