Enclosure NEMA Rating
No Enclosure
Overload Relay Amp Setting
4 to 6.3A
HP @ 3 Phase - 240V
1 1/2 hp
HP @ 1 Phase - 120V
1/4 hp
HP @ 3 Phase - 460-575V
3/5
Phase Loss Sensitivity
Yes
Description/Special Features
Melting Alloy Thermal Overload, Single Unit
HP @ 1 Phase - 230V
1/2 hp
HP @ 3 Phase - 208V
1 1/2 hp
Standards
ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed
Ip Degree Of Protection
IP20 IEC 60529
Magnetic Tripping Current
78-78 A
Device Application
motor protection
Suitability For Isolation
yes IEC 60947-1§ 7-1-6
Mechanical Robustness
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Ambient Air Temperature For Storage
-40-80°C
Thermal Protection Adjustment Range
4-6.3 A IEC 60947-4-1
Product Certifications
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
Trip Unit Technology
thermal-magnetic
Tightening Torque
1.7 N.m screw clamp terminal
Climatic Withstand
IACS E10
Mechanical Durability
100000 cycles
Product Or Component Type
motor circuit breaker
Motor Power Kw
2.2-2.2 kW 400/415 V AC 50/60 Hz || 3-3 kW 500 V AC 50/60 Hz || 4-4 kW 690 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-2
Electrical Durability
100000 cycles AC-3 415 V In
[Ui] Rated Insulation Voltage
690 V AC 50/60 Hz IEC 60947-2
Utilisation Category
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Fixing Mode
35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
Breaking Capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Product Name
TeSys GV2 || TeSys Deca
Phase Failure Sensitivity
yes IEC 60947-4-1
Ambient Air Temperature For Operation
-20-60°C
[Ith] Conventional Free Air Thermal Current
6.3 A IEC 60947-4-1
Fire Resistance
960°C IEC 60695-2-11
Power Dissipation Per Pole
2.5 W
Operating Altitude
6561.68 ft (2000 m)
[Ics] Rated Service Short-Circuit Breaking Capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
Ik Degree Of Protection
IK04
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Network Frequency
50/60 Hz IEC 60947-4-1
Rated Duty
continuous IEC 60947-4-1
Horsepower @ Three Phase - 240V AC
1 1/2 hp
Maximum Operating Temperature
140 Degrees F
Maximum Overload Relay Current Setting
6.3 A
Electrical Operating Durability
100,000
Minimum Overload Relay Current Setting
4 A
Status Indicator
No Indicator
Resistance Properties
Fire Resistant
Terminal Connection Type
Screw Clamp Terminals
NEMA Enclosure Rating
No Enclosure
Minimum Operating Temperature
-4 Degrees F
Horsepower @ Single Phase - 120V AC
1/4 hp
Horsepower @ Three Phase - 208V AC
1 1/2 hp
Overload Protection Type
Thermal
Horsepower @ Single Phase - 240V AC
1/2 hp
Horsepower @ Three Phase - 600V AC
5 hp
Horsepower @ Three Phase - 480V AC
3 hp
Mechanical Operating Durability
100,000
Maximum Voltage Rating
690V AC
Country of Origin (subject to change)
Thailand