Item | Motor Management System |
Current Range | 5 to 100A |
Control Voltage | 24V DC |
Width | 3.58 in |
Interface | DeviceNet |
Operating Voltage | 690V AC |
Height | 2.4 in |
Depth | 4.82 in |
Standards | CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nUL, RMRoS, UL 508 |
For Use With | Short Circuit Protection And A Contactor |
Protective Treatment | 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068 |
Communication Port Protocol | DeviceNet |
Supply Voltage Limits | 20.4-26.24 V DC |
Permissible Power | 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output) |
Maximum Operating Frequency | 2 Hz |
Product Name | TeSys T |
Overvoltage Category | III |
Mechanical Robustness | vibrations mounted on symmetrical rail1 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27 |
Logic Input Number | 6 |
Device Short Name | LTMR |
Product Certifications | RMRoS || ABS || NOM || KERI || RINA || BV || CCC || C-tick || CSA || EAC || ATEX || UL || GL || DNV || LROS (Lloyds register of shipping) |
Network And Machine Diagnosis Type | running hours counter/operating time || starting current and time || trip context information || remaining operating time before overload tripping || fault recording || phase fault and earth fault trip counters || event recording || trip history information || waiting time after overload tripping || motor control command recording |
Fire Resistance | 650°C EN/IEC 60695-2-12 || 960°C UL 94 |
Web Services | web server |
Protection Type | earth-leakage protection || overload || reverse polarity protection || thermal protection || overload (long time) || load fluctuation || phase failure || thermal overload protection || power factor variation || locked rotor || phase unbalance |
Range | TeSys |
Connections - Terminals | control circuit connector 1 0.25-2.5 mm? AWG 24 to AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm? AWG 24 to AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm? AWG 24 to AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm? AWG 24 to AWG 14)solid without cable end |
Current State 1 Guaranteed | logic input < 15 V 2 to 15 mA 15 ms |
Load Current | 5 A 250 V AC logic output || 5 A 30 V DC logic output |
Connection Pitch | 5.08 mm |
Measurement Current | 5-100 A |
Ambient Air Temperature For Storage | -40-80°C |
Associated Fuse Rating | 4 A gG output || 0.5 A gG control circuit |
Pollution Degree | 3 |
Electromagnetic Compatibility | electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 |
Current Consumption | 56 to 127 mA |
Short-Circuit Withstand | 100 kA conforming to EN/IEC 60947-4-1 |
Metering Type | temperature || average current Iavg || imbalance current || earth-fault current || phase current I1, I2, I3 RMS |
Bus Type | DeviceNet ISO 1198 1 to 64 125 to 500 kbit/s, terminal block 4 twisted shielded pairs cable |
Maximum Operating Rate | 1800 cyc/h |
Ip Degree Of Protection | IP20 |
[Ui] Rated Insulation Voltage | 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508 |
[Uimp] Rated Impulse Withstand Voltage | 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1 |
Operating Altitude | <= 6561.68 ft (2000 m) without derating |
Contacts Type And Composition | 1 NO + 1 NC fault signal || 3 NO |
Ambient Air Temperature For Operation | -20-60°C |
[Us] Rated Supply Voltage | 24 V DC |
Tightening Torque | control circuit 0.5-0.6 N.m flat 3 mm |
Product Or Component Type | motor controller |
Compatibility Code | LTMR |
Input Current | 7 mA |
Device Application | equipment monitoring and control |
Measurement Accuracy | 5 to 15 % earth fault current internal measurement || 1 % voltage 100 to 830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current |
Current State 0 Guaranteed | logic input < 5 V <= 15 mA 5 ms |
Overall Width | 3.58 in |
Number of Contacts Included | 5 |
Number of Normally Closed Contacts | 1 |
Number of Normally Open Contacts | 4 |
Minimum Current Rating | 5 A |
Overall Height | 2.4 in |
Maximum Current Rating | 100 A |
Overall Depth | 4.82 in |
Compatible with Series | TeSys T |
Country of Origin (subject to change) | China |
Package Quantity | 1 |
Motor Manager, DeviceNet, 24VDC, 5-100A, SCHNEIDER ELECTRIC, Mfr# LTMR100DBD
$900,99
Free shipping will be applied on orders over $50
Motor Management System, Number of Normally Open Contacts 4, Number of Normally Closed Contacts 1, Number of Contacts Included 5, Operating Voltage 690V AC, Control Voltage 24V DC, Interface DeviceNet, Compatible with Series TeSys T, Overall Width 3.58 in, Standards CSA C22.2 No 14, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nDNV, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nUL, RMRoS, UL 508, Overall Height 2.4 in, Overall Depth 4.82 in, Maximum Current Rating 100 A