Item | Motor Management System |
Current Range | 0.40 to 8A |
Control Voltage | 24V DC |
Width | 3.58 in |
Interface | Modbus |
Operating Voltage | 690V AC |
Height | 2.4 in |
Depth | 4.82 in |
Standards | CSA C22.2 No 14, DNV, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nRMRoS, nUL, UL 508 |
For Use With | Short Circuit Protection And A Contactor |
Network And Machine Diagnosis Type | running hours counter/operating time || trip history information || phase fault and earth fault trip counters || fault recording || waiting time after overload tripping || remaining operating time before overload tripping || trip context information || starting current and time || event recording || motor control command recording |
Permissible Power | 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output) |
Maximum Operating Rate | 1800 cyc/h |
Compatibility Code | LTMR |
Ambient Air Temperature For Operation | -20-60°C |
Connection Pitch | 5.08 mm |
Communication Port Protocol | Modbus |
[Us] Rated Supply Voltage | 24 V DC |
Product Name | TeSys T |
Bus Type | Modbus 2-wire RS 485 1 to 247 1.2 to 19.2 kbit/s, RJ45 2 shielded twisted pairs || Modbus 2-wire RS 485 1 to 247 1.2 to 19.2 kbit/s, terminal block 2 shielded twisted pairs |
Electromagnetic Compatibility | electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 |
Associated Fuse Rating | 4 A gG output || 0.5 A gG control circuit |
Ambient Air Temperature For Storage | -40-80°C |
Supply Voltage Limits | 20.4-26.24 V DC |
Measurement Accuracy | 5 to 15 % earth fault current internal measurement || 1 % voltage 100 to 830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power |
[Uimp] Rated Impulse Withstand Voltage | 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1 |
Input Current | 7 mA |
Ip Degree Of Protection | IP20 |
Short-Circuit Withstand | 100 kA conforming to EN/IEC 60947-4-1 |
Product Or Component Type | motor controller |
Protection Type | phase unbalance || locked rotor || power factor variation || load fluctuation || overload || overload (long time) || phase failure || thermal protection || thermal overload protection || earth-leakage protection || reverse polarity protection |
Overvoltage Category | III |
Load Current | 5 A 250 V AC logic output || 5 A 30 V DC logic output |
Operating Altitude | <= 6561.68 ft (2000 m) without derating |
Contacts Type And Composition | 1 NO + 1 NC fault signal || 3 NO |
Maximum Operating Frequency | 2 Hz |
Measurement Current | 0.4-8 A |
Range | TeSys |
Web Services | web server |
Tightening Torque | control circuit 0.5-0.6 N.m flat 3 mm |
Current Consumption | 56 to 127 mA |
Current State 1 Guaranteed | logic input < 15 V 2 to 15 mA 15 ms |
Connections - Terminals | control circuit connector 1 0.25-2.5 mm? AWG 24 to AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm? AWG 24 to AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm? AWG 24 to AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm? AWG 24 to AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm? AWG 24 to AWG 14)solid without cable end |
Device Application | equipment monitoring and control |
[Ui] Rated Insulation Voltage | 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508 |
Product Certifications | DNV || EAC || ABS || BV || CSA || UL || RINA || RMRoS || CCC || GL || KERI || LROS (Lloyds register of shipping) || NOM || ATEX || C-tick |
Device Short Name | LTMR |
Mechanical Robustness | vibrations mounted on symmetrical rail1 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5 to 300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27 |
Logic Input Number | 6 |
Current State 0 Guaranteed | logic input < 5 V <= 15 mA 5 ms |
Protective Treatment | 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068 |
Metering Type | average current Iavg || earth-fault current || phase current I1, I2, I3 RMS || imbalance current || temperature |
Pollution Degree | 3 |
Fire Resistance | 650°C EN/IEC 60695-2-12 || 960°C UL 94 |
Overall Height | 2.4 in |
Overall Depth | 4.82 in |
Maximum Current Rating | 8 A |
Number of Contacts Included | 5 |
Number of Normally Open Contacts | 4 |
Compatible with Series | TeSys T |
Minimum Current Rating | 0.4 A |
Number of Normally Closed Contacts | 1 |
Overall Width | 3.58 in |
Country of Origin (subject to change) | China |
Package Quantity | 1 |
Motor Manager, Modbus, 24VDC, 0.40-8A, SCHNEIDER ELECTRIC, Mfr# LTMR08MBD
$1044,99
Free shipping will be applied on orders over $50
Motor Management System, Number of Normally Open Contacts 4, Number of Normally Closed Contacts 1, Number of Contacts Included 5, Operating Voltage 690V AC, Control Voltage 24V DC, Interface Modbus, Compatible with Series TeSys T, Overall Width 3.58 in, Standards CSA C22.2 No 14, DNV, EN 60947-4-1, IACSE10, IEC 60947-4-1, nABS, nATEX, nBV, nC-tick, nCCC, nCSA, nEAC, nGL, nKERI, nLROS, nNOM, nRINA, nRMRoS, nUL, UL 508, Overall Height 2.4 in, Overall Depth 4.82 in, Maximum Current Rating 8 A