Frame / Series / Class / Code
Class 8502
Standards
CSA, UL E78351 CCN NLDX
Auxiliary Contact Form
Auxiliary Contacts Not Included
[Uc] Control Circuit Voltage
120 V AC 60 Hz || 110 V AC 50 Hz
Nema Degree Of Protection
NEMA 1 painted sheet steel
Control Circuit
separate control circuit
Local Signalling
no indicator
Rated Power In Hp
3 HP 200 V AC || 3 HP 230 V AC || 5 HP 460 V AC || 5 HP 575 V AC
Contactor Application
non-reversing
Control Type
no control units
[Ue] Rated Operational Voltage
600 V AC
Product Compatibility
circuit-breaker 70 A maximum, SCCR: 100 kA at 480 V AC || fuse J 60 A maximum, SCCR: 100 kA at 600 V AC || fuse T 60 A maximum, SCCR: 100 kA at 600 V AC || fuse RK1 60 A maximum, SCCR: 100 kA at 600 V AC || fuse RK5 60 A maximum, SCCR: 100 kA at 600 V AC
Electrical Connection
screw clamp terminals
Product Or Component Type
contactor
Auxiliary Contact Composition
without
Product Certifications
UL listed file E78351 CCN NLDX || CSA
Reversing Capability
Non-Reversing
Embedded Surge Suppressor
No
Terminal Connection Type
Screw Clamp Terminals
Horsepower @ Three Phase - 600V AC
5 hp
Maximum Voltage Rating
600V AC
Full Load Current - Inductive
18 A
Horsepower @ Three Phase - 208V AC
3 hp
Horsepower @ Three Phase - 240V AC
3 hp
Includes Auxiliary Contacts
No
NEMA Enclosure Material
Steel
Horsepower @ Single Phase - 240V AC
3 hp
Number of Auxillary Contacts
0
Horsepower @ Three Phase - 480V AC
5 hp
Country of Origin (subject to change)
Mexico