NEMA Rating
1, 12, 13, 2, 3, 3R, 4, 6
Type of Operator
Extended Button
Bezel
Chrome Plated Zinc Die Cast
Contact Rating
10A @ 600V AC
Item
Extended Push Button Operator
Features
Finger-Safe Terminals
Terminal Connection
Screw Clamp
Standards
CSA C22.2 No.14, EN/IEC 60947-1, EN/IEC 60947-5-1, EN/IEC 60947-5-4, JIS C4520, JIS C852, REACH, RoHS, UL 508, WEEE
NEMA Contact Rating Designation
A600/Q600
Lamp Module Type
Not Applicable
AC Contact Rating
1.2 A @ 600 V, 1.5 A @ 480 V, 3 A @ 240 V, 6 A @ 120 V
DC Contact Rating
0.1 A @ 600 V, 0.27 A @ 250 V, 0.55 A @ 125 V
Product Type
Push Button Operators
Shape Of Signaling Unit Head
octagonal
Shape Of Screw Head
cross slotted
[Icm] Rated Short-Circuit Making Capacity
12 kA 600 V AC-15, 7200 VA || 15 kA 480 V AC-15, 7200 VA || 30 kA 240 V AC-15, 7200 VA || 60 kA 120 V AC-15, 7200 VA || 0.1 kA 600 V DC-13 || 0.27 kA 250 V DC-13 || 0.55 kA 125 V DC-13
Contacts Type And Composition
1 NC
Shock Resistance
50 gn IEC 60068-2-27
Ambient Air Temperature For Operation
-25-70°C
[Ie] Rated Operational Current
3 A 240 V, AC-15, A600-Q600 NEMA || 0.55 A 125 V, DC-13, A600-Q600 NEMA
Operator Profile
red projecting, unmarked, projecting
Connections - Terminals
screw clamp terminals 1 x 0.22 to 2 x 1.5 mm² IEC 60947-1
Contact Operation
standard
Operating Position
any position
Cap/Operator Or Lens Colour
red
Contacts Material
silver alloy contacts
Electrical Shock Protection Class
class II IEC 61140
Tightening Torque
0.8-0.8 N.m IEC 60947-1
Ambient Air Temperature For Storage
-40-70°C
Ip Degree Of Protection
IP66 IEC 60529
Device Presentation
complete product
Product Certifications
NEMA || UL 508
[Ui] Rated Insulation Voltage
250 V 3)IEC 60947-1
[Ith] Conventional Free Air Thermal Current
10 A
Product Or Component Type
push-button
Short-Circuit Protection
10 A cartridge fuse IEC 60947-5-1
Positive Opening
with IEC 60947-5-2
Operator Additional Information
without guard
Nema Degree Of Protection
NEMA 1 || NEMA 12 || NEMA 13 || NEMA 2 || NEMA 3 || NEMA 3R || NEMA 4
Vibration Resistance
7 gn 2-500 Hz)IEC 60068-2-6
Rated Breaking Capacity
3 kA 240 V AC-15, 720 VA || 6 kA 120 V AC-15, 720 VA || 1.2 kA 600 V AC-15, 720 VA || 1.5 kA 480 V AC-15, 720 VA || 0.1 kA 600 V DC-13 || 0.27 kA 250 V DC-13 || 0.55 kA 125 V DC-13
Terminals Description Iso N°1
(21-22)NC
Mechanical Durability
5000000 cycles
[Uimp] Rated Impulse Withstand Voltage
2.5 kV IEC 60947-1
Terminals Description Iso N°1
(21-22)NC
Hazardous Location Specification
Class I, Div 2, Group A, Class I, Div 2, Group B, C, D, Class II, Div 2, Group E, F, Class II, Div 2, Group G, Class III, Div 1 and 2
Number of Indicator Lights
0
Legend Background Color
Not Applicable
NEMA Enclosure Rating
1, 12, 13, 2, 3, 3R, 4
Maintained Action Release
Not Applicable
Operating Temperature - Maximum
158 Degrees F
Resistance Properties
Corrosion Resistant, Dust Resistant, Impact Resistant, Vibration Resistant, Watertight
Lamp Voltage - Maximum
Not Applicable
Operator Voltage Rating - Maximum
600 V AC
Push Button Style
Extended
Mechanical Operating Durability
5.00 x 10^6
Operating Temperature - Minimum
-13 Degrees F
Manufacturer Warranty Length
18 mo
Legend Color
Not Applicable
Panel Cutout Diameter
30 mm
Operator Illumination
Non-Illuminated
Mushroom Head Diameter
Not Applicable
Country of Origin (subject to change)
Mexico