Item - Relay
IEC Style Overload Relay
Current Range
0.23 to 0.36A
Use With - Contactors and Starters
LC7K, LP1K, LP4K Contactors, Mfr. Series LC1K
Overload Relay Current Range
0.23 to 0.36A
Reset Type - Relay
Auto, Manual
For Use With
TeSys K AC or DC IEC Contactor
Body Height - Relay
2.28 in
Features
Single Phase Sensitivity; Differential
Overall Height - Relay
2.28 in
Body Width - Relay
1.77 in
Standards
BS 4941, IEC 60947, NF C 63-650, REACH, RoHS, VDE 0660
Body Depth - Relay
2.56 in
Connections - Terminals
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
Control Type
Red push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
[Uimp] Rated Impulse Withstand Voltage
6 kV
Auxiliary Contact Composition
1 NO + 1 NC
Power Dissipation Per Pole
2 W
Thermal Overload Class
class 10A IEC 60947-4-1
Local Signalling
trip indicator Yellow)
Operating Altitude
6561.68 ft (2000 m) without derating
Thermal Protection Adjustment Range
0.23-0.36 A
[Ith] Conventional Free Air Thermal Current
6 A signalling circuit
[Ui] Rated Insulation Voltage
power circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
Product Or Component Type
differential thermal overload relay
[Ue] Rated Operational Voltage
u003c= 690 V power circuit || 690 V AC AC-15 signalling circuit || 250 V DC DC-13 signalling circuit
Product Compatibility
LC7K || LC1K || LP1K || LP4K
Ambient Air Temperature For Operation
-20-55°C without derating IEC 60947 || -30-60°C with derating IEC 60947
Associated Fuse Rating
6 A gG signalling circuit VDE 0660 || 6 A gG signalling circuit IEC 60947
Mounting Support
under contactor || plate, with specific accessories || rail, with specific accessories
Phase Failure Sensitivity
yes IEC 60947-4-1
Network Frequency
u003c= 400 Hz
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage
-40-70°C
Ip Degree Of Protection
IP2X conforming to IEC 60529
Tightening Torque
1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Relay Application
motor protection
Protective Treatment
TC IEC 60068 || TC DIN 50016
Mechanical Robustness
shocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5 to 300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5 to 300 Hz IEC 60068-2-6
Fire Resistance
850°C IEC 60695-2-1
Product Certifications
UL || CSA || UKCA
Maximum Operating Temperature
131 Degrees F
Mounting Style
Direct To Contactor
Minimum Operating Temperature
-4 Degrees F
Terminal Connection Type
Screw Clamp Terminals
Auxiliary Contact Form
1NO/1NC
Maximum Overload Relay Current Setting
0.36 A
Maximum Voltage Rating
250V DC (Signaling Circuit), 690V AC (Signaling Circuit)
Overload Protection Type
Thermal
Compatible with Series
TeSys Deca, TeSys K
Minimum Overload Relay Current Setting
0.23 A
Includes Mounting Hardware
Not Applicable
Country of Origin (subject to change)
Czechia