Item - Relay
IEC Style Overload Relay
Use With - Contactors and Starters
Mfr. Series LC1D09 to LC1D32 Contactors
Current Range
7.00 to 10.0A
Overload Relay Current Range
7.0 to 10.0A
Body Height - Relay
2.99 in
Body Width - Relay
1.77 in
For Use With
TeSys D 9-32A, TeSys N Size 00-1 Contactors
Overall Height - Relay
2.99 in
Standards
CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EN 50495, EN/IEC 60947-4-1, EN/IEC 60947-5-1, REACH, RoHS, UL 60947-4-1, UL 60947-5-1
Permissible Current
3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
Product Name
TeSys LRD || TeSys Deca
Connections - Terminals
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit screw clamp terminals 1 1.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-4 mm² flexible with cable end || power circuit screw clamp terminals 1 1-6 mm² solid without cable end
Relay Application
motor protection
[Ue] Rated Operational Voltage
690 V AC 0 to 400 Hz power circuit IEC 60947-4-1
Ambient Air Temperature For Storage
-60-70°C
Product Compatibility
LC1D25 || LC1D18 || LC1D38 || LC1D12 || LC1D09 || LC1D32
Phase Failure Sensitivity
tripping current 130 % of Ir on two phase, the last one at 0
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Product Or Component Type
non differential thermal overload relay
Ambient Air Temperature For Operation
-20-60°C without derating IEC 60947-4-1
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Thermal Overload Class
class 20 IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage
6 kV
Auxiliary Contact Composition
1 NO + 1 NC
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Mechanical Robustness
shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations3 GN IEC 60068-2-6
Network Frequency
0 to 400 Hz
Ip Degree Of Protection
IP20 conforming to IEC 60529
Temperature Compensation
-20-60°C
Control Type
Red push-button stop || Blue push-button reset
Product Certifications
IEC || UL || CSA || EAC || ABS || ATEX INERIS || UKCA
Associated Fuse Rating
4 A gG signalling circuit || 4 A BS signalling circuit
Climatic Withstand
IACS E10
Thermal Protection Adjustment Range
7-10 A
Tightening Torque
control circuit 1.7 N.m screw clamp terminals || power circuit 1.7 N.m screw clamp terminals
Tripping Threshold
1.14 +/- 0.06 Ir IEC 60947-4-1
Mounting Support
plate, with specific accessories || rail, with specific accessories || under contactor
Maximum Voltage Rating
690V AC
Includes Mounting Hardware
Not Applicable
Mounting Style
Direct To Contactor
Terminal Connection Type
Screw Clamp Terminals
Compatible with Series
TeSys Deca
Overload Protection Type
Thermal
Minimum Operating Temperature
-4 Degrees F
Maximum Overload Relay Current Setting
10 A
Minimum Overload Relay Current Setting
7 A
Maximum Operating Temperature
140 Degrees F
Auxiliary Contact Form
1NO/1NC
Country of Origin (subject to change)
Thailand