Full Load Amps-Inductive
25 A
Full Load Amps-Resistive
40 A
HP @ 3 Phase - 240V
7 1/2 hp
Auxiliary Contact Form
2NO/2NC
Series
SIRIUS 3RT Safety Contactors
Standards
REACH Art 33, WEEE (2012/19/EU)
Frame / Series / Class / Code
S0
Aux. Contact Configuration
2NO/2NC
Power loss, static, current-independent [Pls]
5.9 watt
suitable for series installation
Yes
Rated operating power with AC-3, 400 V
11 kilowatt
rated operational power AC-1 at 400 V
23 kilowatt
Number of making contacts and main contacts
3
Rated current [In] for the power loss specification
25 ampere
min. rated control voltage Us with DC
24 volt
Power loss per pole, current-dependent [PlIp]
1.9 watt
Rated operating current Ie with AC-3, 400 V
25 ampere
Connection type
Screw connection
Full Load Current - Inductive
25 A
Mounting Hole Distance - Width
1.38 in
Mounting Hole Diameter
0.19 in
Horsepower @ Three Phase - 480V AC
15 hp
Number of Normally Open Main Contacts
3
Maximum Operating Temperature
140 Degrees F
Horsepower @ Single Phase - 120V AC
2 hp
NEMA Enclosure Rating
No Enclosure
Horsepower @ Single Phase - 240V AC
3 hp
Maximum Voltage Rating
690V AC
Minimum Operating Temperature
-13 Degrees F
Reversing Capability
Non-Reversing
Horsepower @ Three Phase - 240V AC
7 1/2 hp
Number of Auxillary Contacts
4
Terminal Connection Type
Screw Terminals
Mounting Hole Distance - Height
2.36 in
Embedded Surge Suppressor
Yes
Horsepower @ Three Phase - 600V AC
20 hp
Includes Auxiliary Contacts
Yes
Mounting Style
DIN Rail, Surface
Full Load Current - Resistive
40 A
Response Time
10 to 17 msec (AC Operation Closing Delay Operation Opening Delay Operating Times for 1.0 x Us1), 15 to 17.5 msec (DC Operation Opening Delay Operating Times For 0.8 ... 1.1 X Us1), 16 to 17 msec (DC Operation Opening Delay Operating Times for 1.0 x Us), 4 to 16 msec (AC Operation Opening Delay Operating Times for 0.8 ... 1.1 X Us1), 4 to 16 msec (AC Operation Opening Delay Operating Times for 1.0 x Us), 50 to 170 msec (DC Operation Closing Delay Operating Times for 0.8 ... 1.1 X Us1), 55 to 80 msec (DC Operation Closing Delay Operating Times for 1.0 x Us), 8 to 40 msec (AC Operation Closing Delay)
Mechanical Operating Durability
10,000,000
Horsepower @ Three Phase - 208V AC
5 hp
Country of Origin (subject to change)
Germany