Item | Electronic Pressure Sensor |
Range | -0.7 to 14.5 psi |
Analog Output | 4 to 20mA or 0 to 10V DC |
Control Output | PNP |
On/Off Setting | Programmable |
Max. Pressure | 450 psi |
Power Required | 18 to 30V DC |
Process Connection | 1/4 in NPT |
Electrical Connection | 4 Pin M12 |
Display | 4 Digit LED |
Operating Temp. Range | -13 Degrees to 176 Degrees F |
IP Rating | 65/67 |
Housing Material | Stainless Steel |
Standards | CE, CULus |
Wetted Materials | Stainless Steel |
Application | for industrial applications |
Min. load resistance [?] | 2000 |
Protection | IP 65, IP 67 |
Permanent current rating of switching output DC [mA] | 250 |
Max. load [?] | 500 |
Max. voltage drop switching output DC [V] | 2 |
Reverse polarity protection | yes |
Integrated watchdog | yes |
Hysteresis deviation [% of the span] | <± 0,1, (Turn down 1:1) |
Vacuum resistance [mbar] | -1000 |
IO-Link process data (cyclical) | function bit length pressure 14 binary switching information 2, function bit length pressure 16 device status 4 binary switching information 2 |
Communication interface | IO-Link |
IO-Link functions (acyclical) | application specific tag |
Delay time programmable dS, dr [s] | 0...50 |
Output signal | switching signal, analogue signal, IO-Link, (configurable) |
Min. bursting pressure | 30000 mbar 450 psi 3000 kPa |
Max. response time analogue output [ms] | 3 |
Number of analogue outputs | 1 |
Analogue voltage output [V] | 0...10, (scalable 1:5) |
Protection class | III |
Min. insulation resistance [M?] | 100, (500 V DC) |
Min. pressure cycles | 100 million |
IO-Link resolution pressure [mbar] | 0.5, 1 |
Short-circuit protection | yes |
Restrictor element integrated | no (can be retrofitted) |
MAWP (for applications according to CRN) | 10 bar 10000 mbar 145 psi 1000 kPa |
Reset point rP | -48...996 mbar -0.69...14.44 psi -19.2...399.8 inH2O -4.8...99.6 kPa, -48...996 mbar -0.7...14.44 psi -19...400 inH2O -4.4...99.6 kPa |
Response time [ms] | < 1.5 |
Electrical design | PNP/NPN |
SIO mode | yes |
Measuring range | -0.05...1 bar -50...1000 mbar -0.72...14.5 psi -20.1...401.5 inH2O -5...100 kPa |
Number of digital outputs | 2 |
Transmission type | COM2 (38,4 kBaud) |
Repeatability [% of the span] | <± 0,1, (with temperature fluctuations < 10 K, Turn down 1:1) |
Materials | stainless steel (1.4404 / 316L), PBT+PC-GF30, PBT-GF20, PC |
Power-on delay time [s] | 0.3 |
Ambient temperature [°C] | -25...80 |
Switch point accuracy [% of the span] | <± 0,4, (Turn down 1:1) |
Analogue current output [mA] | 4...20, (scalable 1:5) |
Analogue end point | 150...1000 mbar 2.18...14.5 psi 60.5...401.5 inH2O 15...100 kPa |
Characteristics deviation [% of the span] | <± 0,25 (BFSL) / <± 0,5 (LS), (Turn down 1:1, BFSL = Best Fit Straight Line, LS = limit value setting) |
Type of pressure | relative pressure |
Profiles | Smart Sensor: Process Data Variable, Device Identification, Device Diagnosis, Smart Sensor ED2: Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
IO-Link revision | 1.1 |
Output function | normally open / normally closed, (parameterisable) |
Shock resistance | DIN EN 60068-2-27 50 g (11 ms) |
Connection | Connector: 1 x M12, coding: A, Contacts: gold-plated |
Materials (wetted parts) | stainless steel (1.4404 / 316L), AI2O3 (96%, ceramics), FKM |
Damping for the analogue output dAA [s] | 0...4 |
Operating voltage [V] | 18...30 DC, (to SELV/PELV) |
UL approval | UL Approval no. J012 |
Min. process cycle time [ms] | 2.3, 3 |
Total number of outputs | 2 |
Temperature coefficient zero point [% of the span / 10 K] | <± 0,2, (-0...80°C) |
EMC | DIN EN 61000-6-2 DIN EN 61000-6-3 |
Required master port type | A, (when pin 2 not connected: B) |
Medium temperature [°C] | -25...80 |
In steps of | 2 mbar 0.02 psi 0.5 inH2O 0.2 kPa, 1 mbar 0.01 psi 0.1 inH2O 0.1 kPa |
Parameter setting options | hysteresis / window, normally open / normally closed, switch-on/switch-off delay, Damping, Display unit, current/voltage output |
Storage temperature [°C] | -40...100 |
Special feature | Gold-plated contacts |
Temperature coefficient span [% of the span / 10 K] | <± 0,2, (-0...80°C) |
SDCI standard | IEC 61131-9 |
Vibration resistance | DIN EN 60068-2-6 20 g (10...2000 Hz) |
Type of short-circuit protection | pulsed |
Pressure Equipment Directive | Sound engineering practice, can be used for group 2 fluids, group 1 fluids on request |
Pressure rating | 10000 mbar 145 psi 1000 kPa |
Long-term stability [% of the span] | <± 0,05, (Turn down 1:1, per 6 months) |
MTTF [years] | 138 |
Analogue start point | -50...800 mbar -0.72...11.6 psi -20...321 inH2O -5...80 kPa |
Number of inputs and outputs | Number of digital outputs: 2, Number of analogue outputs: 1 |
Min. difference between SP and rP | 6 mbar 0.06 psi 2 inH2O 0.6 kPa, 5 mbar 0.06 psi 1.7 inH2O 0.5 kPa |
Current consumption [mA] | < 35 |
Media | liquids and gases |
Set point SP | -44...1000 mbar -0.63...14.5 psi -17.5...401.5 inH2O -4.4...100 kPa, -44...1000 mbar -0.64...14.5 psi -17.5...401.5 inH2O -4.4...100 kPa |
Measuring element | ceramic-capacitive pressure measuring cell |
Damping process value dAP [s] | 0...4 |
Switching frequency DC [Hz] | < 500 |
Overload protection | yes |
Tightening torque [Nm] | > 50, (depends on lubrication, seal and pressure rating) |
Country of Origin (subject to change) | Germany |
Package Quantity | 1 |
Pressure Sensor, Range -0.7 to 14.5 psi, IFM, Mfr# PN2297
$439,99
Free shipping will be applied on orders over $50
Electronic Pressure Sensor, Range -0.7 to 14.5 psi, Analog Output 4 to 20mA or 0 to 10V DC, Control Output PNP, Programmable On/Off Setting, Power Required 18 to 30V DC, Process Connection 1/4 in NPT, Electrical Connection 4 Pin M12, Display 4 Digit LED, Wetted Materials Stainless Steel, Housing Material Stainless Steel, Operating Temp. Range -13 Degrees to 176 Degrees F, IP Rating 65/67, Max. Pressure 450 psi, Standards CE, CULus
9999 in stock
Must order in multiples of 1
Subtotal:
$439.99
You must be logged in to post a review.
Reviews
There are no reviews yet.