Electrical Endurance
100,000 operations @ 5 A resistive load
Protocols
Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, HTTP
I/O Mode
DI or Event Counter
Wet Contact (DI to COM)
On: 10 to 30 VDC; Off: 0 to 3 VDC
Hazardous Location
UL/cUL Class I Diision 2, ATEX Zone 2
Contact Current Rating
Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Dimensions
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Operating temperature
Standard Models: -10 to 60°C (14 to 140°F); Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Dry Contact
On: short to GND; Off: open
Ambient Relative Humidity
5 to 95% (non-condensing)
Power Consumption
188 mA @ 24 VDC
Database
Telcordia (Bellcore)
EMI
EN 55022; EN 61000-3-2; EN 61000-3-3; FCC Part 15, Subpart B, Class A
Initial Insulation Resistance
1000 M ohms (min.) @ 500 VDC
Storage temperature
-40 to 85°C (-40 to 185°F)
Protection
1.5 kV magnetic isolation
Power Input
24 VDC nominal, 12 to 36 VDC
Ethernet
2 switched 10/100 Mbps RJ45 ports
EMS
EN 55024, EN 61000-4-2, EN 61000-4-3; EN 61000-4-4, EN 61000-4-5, EN 61000-4-6; EN 61000-4-8, EN 61000-4-11
Relay On/Off Time
1500 ms (max.)
Isolation
3k VDC or 2k Vrms
Wiring
I/O cable max. 14 AWG
Pulse Output
0.3 Hz at rated load
Common Type
6 points per COM
Contact Resistance
100 m ohms (max.)
Type
Form A (N.O.) power relay
Digital Filtering Time Interval
Software Configurable
Mechanical Endurance
5,000,000 operations
Sensor Type
Wet Contact (NPN or PNP), Dry Contact
Country of Origin (subject to change)
Taiwan, Province of China