Item
Safety Interlock Switch
Standards
ISO 14119 || EN/ISO 12100 || EN/IEC 60947-5-1 || CSA C22.2 No 14 || EN/IEC 60204-1 || UL 508
Electrical Connection
pre-cabled
Shock Resistance
30 gn 11 ms IEC 60068-2-27
Electrical Durability
1200000 cycles
Vibration Resistance
10 gn 10-150 Hz)IEC 60068-2-6
Maximum Sensitivity To Magnetic Fields
0.3 mT
[Ue] Rated Operational Voltage
24 V DC
[Sar] Assured Tripping Distance
15 mm
[Sa] Assured Operating Distance
5 mm
Ip Degree Of Protection
IP66 conforming to IEC 60529 || IP67 conforming to IEC 60529
Approach Directions
3 directions
Maximum Switching Voltage
100 V DC
[Uimp] Rated Impulse Withstand Voltage
2.5 kV EN/IEC 60947-5-1
Maximum [Ie] Rated Operational Current
100 mA
Cable Composition
4 x 0.25 mm²
Contact Operation
staggered
Ambient Air Temperature For Storage
-40-85°C
Safety Level
can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508
Switching Frequency
150 Hz
[Ui] Rated Insulation Voltage
100 V DC
Contacts Type And Composition
1 NC + 1 NO
Electrical Shock Protection Class
class II EN/IEC 61140
Switching Capacity In Ma
0.1...100 mA
Product Certifications
UL || CSA
Insulation Resistance
1000 MOhm
Enclosure Material
thermoplastic PBT
Design
rectangular, compact
Product Or Component Type
coded magnetic switch
Short-Circuit Protection
500 mA external cartridge fuse gG (gl)
Resistance Across Terminals
10 Ohm
Ambient Air Temperature For Operation
-25-85°C
Country of Origin (subject to change)
France