For Use With
TeSys Series GV2 and GV3 Starters
Features
Shunt, 220 to 240V AC 60 Hz
Accessory Type
Shunt Release
Compatible with Series
TeSys Deca
Standards
CCC, CSA, EAC, IEC, REACH, RoHS, UL Listed
Tightening Torque
u003c 1.4 N.m screw clamp terminals
Mechanical Durability
10000 cycles with GV3P and GV3L || 30000 cycles with GV2ME and GV2P
[Uc] Control Circuit Voltage
220...240 V AC 60 Hz
Connections - Terminals
screw clamp terminals 1 1-2.5 mm²solid || screw clamp terminals 2 1-2.5 mm²solid || screw clamp terminals 1 0.75-2.5 mm²flexible without cable end || screw clamp terminals 2 0.75-2.5 mm²flexible without cable end || screw clamp terminals 1 0.75-1.5 mm²flexible with cable end || screw clamp terminals 2 0.75-1.5 mm²flexible with cable end
Range Compatibility
TeSys GV2ME || TeSys GV2LE || TeSys GV2L || TeSys GV2P || TeSys GV3L || TeSys GV3P || TeSys Deca
[Ui] Rated Insulation Voltage
690 V AC IEC 60947-1 || 600 V AC UL 60947-4-1 || 600 V AC CSA C22.2 No 60947-4-1
Control Circuit Voltage Limits
0.7...1.1 Un
Hold-In Power Consumption In Va
5-5 VA AC
Product Or Component Type
shunt trip release
Hold-In Power Consumption In W
1.6-1.6 W
Inrush Power In Va
14-14 VA AC
Threshold Tripping Voltage
0.75...0.2 Un
Operating Time
10...15 ms IEC 60947-1
Country of Origin (subject to change)
Czechia