Item | Overload Module |
Overload Relay Amp Setting | 0.35 to 1.4 A |
Coil Volts | 110 to 240V AC, 110 to 220V DC |
Number of Poles | 3 |
Features | Protection against phase failure and phase imbalance, Protection against overload and short-circuit, Manual reset, Earth fault protection, Free of Halogen, Mercury & Pvc, Resistance to Fire, Electrostatic Discharge, Fast Transients, Radiated Fields, Shock & Vibration |
Height | 66 mm |
Depth | 60 mm |
Standards | CSA C22.2 No 60947-4-1, EN 60947-6-2, IEC 60947-6-2, REACH, RoHS, UL Listed 60947-4-1 |
Width | 45 mm |
Hz | 40 to 60 Hz |
Body Depth - Relay | 2.36 in |
Reset Type - Relay | Manual |
Sensing Method | Thermal |
Body Width - Relay | 1.77 in |
Overload Relay Current Range | 0.35 to 1.4A |
Item - Relay | IEC Style Overload Relay |
Kit Required for Retrofit Mtg. | No |
Overall Height - Relay | 2.6 in |
Frame / Series / Class / Code | Class 10 |
Use With - Contactors and Starters | Mfr. Series LUA1C Contactors |
Trip Class - Overload | 10 |
Separate Mounting | No |
Body Height - Relay | 2.6 in |
Weight | 0.135 kg |
Operating Voltage | 690V AC |
Maximum Voltage Rating | 690V AC |
Phase | Three |
Compatible with Series | TeSys Ultra |
Minumum Rated Motor Current Adjustment | 0.35 A |
Maximum Operating Temperature | 158 Degrees F |
Minimum Operating Temperature | -13 Degrees F |
Coil Voltage | 110-240V AC/DC |
Compatible with Manufacturer Model Number | LUB12, LUB32, LUB38 |
Maximum Rated Motor Current Adjustment | 1.4 A |
Trip Class | 10 |
Reset Type | Manual |
Operating Time | 35 ms opening with LUB12 control circuit, 35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit, 50 ms closing with LUB12 control circuit, 50 ms closing with LUB32 control circuit, 50 ms closing with LUB38 control circuit |
Immunity To Radioelectric Fields | 10 V IEC 61000-4-6 |
IP Degree Of Protection | IP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1, IP40 front panel outside connection zone IEC 60947-1 |
Utilisation Category | AC-44, AC-41, AC-43 |
Fixing Mode | Plug-in front face) |
Typical Current Consumption | 280 mA 110 to 240 V AC I maximum while closing with LUB12, 280 mA 110 to 240 V AC I maximum while closing with LUB32, 280 mA 110 to 240 V AC I maximum while closing with LUB38, 280 mA 110 to 220 V DC I maximum while closing with LUB12, 280 mA 110 to 220 V DC I maximum while closing with LUB32, 280 mA 110 to 220 V DC I maximum while closing with LUB38, 35 mA 110 to 240 V AC I rms sealed with LUB12, 25 mA 110 to 240 V AC I rms sealed with LUB32, 25 mA 110 to 240 V AC I rms sealed with LUB38, 35 mA 110 to 220 V DC I rms sealed with LUB12, 25 mA 110 to 220 V DC I rms sealed with LUB32, 25 mA 110 to 220 V DC I rms sealed with LUB38 |
Protective Treatment | TH IEC 60068 |
Device Application | Motor control, Motor protection |
Compatibility Code | LUCA |
Thermal Overload Class | Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) IEC 60947-6-2, Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) UL 508 |
Non-Dissipating Shock Wave | 1 kV serial mode IEC 60947-6-2, 2 kV common mode IEC 60947-6-2 |
Load Type | 3-phase motor self-cooled |
Shock Resistance | 10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27 |
Heat Dissipation | 2 W control circuit with LUB12, 3 W control circuit with LUB32, 3 W control circuit with LUB38 |
Fire Resistance | 1760°F (960°C) parts supporting live components IEC 60695-2-12, 1202°F (650°C) IEC 60695-2-12 |
Product Certifications | CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine |
Tripping Threshold | 14.2 x Ir +/- 20% |
Resistance To Radiated Fields | 9.14 V/m (10 V/m) 3 IEC 61000-4-3 |
Operating Altitude | 6561.68 ft (2000 m) |
Ambient Air Temperature For Operation | -13 to 158°F (-25 to 70°C) |
Control Circuit Voltage | 110 to 240 V AC, 110 to 220 V DC |
Product Or Component Type | Standard control unit |
Motor Power KW | 0.25 kW 400 to 440 V AC 50/60 Hz |
Ambient Air Temperature For Storage | -40 to 185°F (-40 to 85°C) |
Main Function Available | Protection against phase failure and phase imbalance, Protection against overload and short-circuit, Manual reset, Earth fault protection |
Safe Separation Of Circuit | 400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1 |
Product Compatibility | Power base LUB12, Power base LUB32, Power base LUB38, Power base LUB120, Power base LUB320, Power base LUB380, Reversing contactor breaker LU2B12FU, Reversing contactor breaker LU2B32FU, Reversing contactor breaker LU2B38FU |
Resistance To Electrostatic Discharge | 8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2 |
Rated Insulation Voltage | 690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1 |
Product Specific Application | Basic protection requirements for motor starters: overload and short-circuit |
Control Circuit Voltage Limits | 88 to 264 V AC 110 to 240 V in operation, 88 to 242 V DC 110 to 220 V in operation, 55 V AC 110 to 240 V drop-out, 55 V DC 110 to 220 V drop-out |
Rated Operational Voltage | 690 V AC |
Vibration Resistance | 2 gn 5 to 300 Hz power poles open IEC 60068-2-6, 4 gn 5 to 300 Hz power poles closed IEC 60068-2-6 |
Immunity To Voltage Dips | 70% / 500 ms IEC 61000-4-11 |
Phase Failure Sensitivity | Yes |
Rated Impulse Withstand Voltage | 6 kV IEC 60947-6-2 |
Immunity To Microbreaks | 3 ms |
Resistance To Fast Transients | 2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4 |
Compatible Manufacturer Part Number | LUB12, LUB32, LUB38 |
Country of Origin (subject to change) | France |
Package Quantity | 1 |
Stdcntrlunitcl103Ph 0314A 110240Vac, 110 to 240V AC; 110 to 220V DC, 3 Poles, SCHNEIDER ELECTRIC, Mfr# LUCA1XFU
$122.21
Free shipping will be applied on orders over $50
Overload Module, Maximum Rated Motor Current Adjustment 1.4 A, Minumum Rated Motor Current Adjustment 0.35 A, Coil Voltage 110-240V AC/DC, Compatible with Series TeSys Ultra, Trip Class 10, Phase Three, Maximum Voltage Rating 690V AC, Reset Type Manual, Standards CSA C22.2 No 60947-4-1, EN 60947-6-2, IEC 60947-6-2, REACH, RoHS, UL Listed 60947-4-1, Compatible with Grainger Part Number 5AB63, 5AB64, Maximum Operating Temperature 158 Degrees F, Minimum Operating Temperature -13 Degrees F