Item | Additional pole |
Voltage | 690V AC |
Standards | CSA C22.2 No 14, IEC 60947-3, UL 508 |
Description/Special Features | Mercury Free, REACh Free of SVHC, RoHS Exemption Information, Toxic Heavy Metal Free |
Depth | 1.72 in |
Max. Voltage | 8 kV |
Height | 3.07 in |
Width | 0.47 in |
For Use With | TeSys VLS Series |
Accessory Type | Additional pole |
Product Type | Additional Pole |
Mounting Mechanism | Door |
Resistance Properties | Fire-Resistant |
Color | Gray |
Voltage Rating | 690V AC |
Mounting Style | Door |
Compatible with Manufacturer Model Number | VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 |
Maximum Voltage | 690V AC |
Door Handle Color | Gray |
UL 508 Certification | Yes |
Current Rating | 40 A |
Ambient Air Temperature For Operation | -25-55°C |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Product Or Component Type | additional pole |
Performance Level | high performance |
Range Compatibility | TeSys (TeSys VARIO LS) VLS3P |
Network Type | AC |
Product Certifications | cULus || GL |
Network Frequency | 50/60 Hz |
Mechanical Robustness | vibrations 2 to 100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27 |
[Ithe] Conventional Enclosed Thermal Current | 40 A |
Tightening Torque | power circuit 1.8-2 N.m screw clamp terminals |
[Icm] Rated Short-Circuit Making Capacity | 1128 A 690 V |
Contacts Type And Composition | 1 NO |
Contact Operation | simultaneous |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
[Icw] Rated Short-Time Withstand Current | 800 A 690 V 1 s |
Mechanical Durability | 100000 cycles |
Suitability For Isolation | yes |
Mounting Support | door |
[Ie] Rated Operational Current | 40 A Ue: 600 V UL 508 || 40 A AC-21A Ue: 400 V || 40 A AC-21A Ue: 500 V || 40 A AC-21A Ue: 690 V || 40 A AC-22A Ue: 400 V || 40 A AC-22A Ue: 500 V || 40 A AC-22A Ue: 690 V || 40 A AC-23A Ue: 400 V || 25 A AC-23A Ue: 500 V || 25 A AC-23A Ue: 690 V |
Electrical Durability | 100000 cycles AC-21A |
Ip Degree Of Protection | IP20 conforming to IEC 60529 |
Intermittent Duty Class | class 120 - 60 % |
Connections - Terminals | power circuit screw clamp terminals 10-10 mm? solid || power circuit screw clamp terminals 16-16 mm? flexible - without cable end |
Device Short Name | VLS1P |
Poles Description | 1P |
[Ith] Conventional Free Air Thermal Current | 40 A 55°C |
Mounting Location | right || left |
Rated Operational Power In W | 18.5 kW 400 V AC-23A) || 18.5 kW 500 V AC-23A) || 22 kW 690 V AC-23A) |
Fire Resistance | 960°C IEC 60695-2-11 |
Making Capacity | 60 A 690 V AC-21A || 120 A 690 V AC-22A || 400 A 690 V AC-23A |
Breaking Capacity | 60 A 690 V AC-21A) || 120 A 690 V AC-22A) || 320 A 690 V AC-23A) |
Rated Conditional Short-Circuit Current | 50 kA 400 V 40 A gG |
Compatible Manufacturer Part Number | VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 |
Compatible with Manufacturer Part Number | VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 |
Compatible with Manufacturer Model Number [NEW] | VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 |
Country of Origin (subject to change) | Italy |
Package Quantity | 1 |
Additional pole, 40 A, 690V AC, Gray, SCHNEIDER ELECTRIC, Mfr# VLS1P040D1S
$24,19
Free shipping will be applied on orders over $50
Additional pole, Color Gray, Compatible with Grainger Part Number 615A62, 615A64, 615A66, 615A67, Compatible with Manufacturer Model Number VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1, Current Rating 40 A, Depth 1.72 in, For Use With TeSys VLS Series, Height 3.07 in, Maximum Voltage 690V AC, Mounting Mechanism Door, Product Type Additional Pole, Resistance Properties Fire-Resistant, Standards CSA C22.2 No 14, IEC 60947-3, UL 508, Width 0.47 in