Contact Rating
10A @ 600V AC
For Use With
Schneider 9001K Series 30mm Operators
Application
Finger Safe Operator
Terminal Connection
Screw/Clamp
NEMA Contact Rating Designation
A600/Q600
Standards
CSA C22.2 No.14, EN, IEC 60947-1, IEC 60947-5-1, IEC 60947-5-4, JIS C4520, JIS C852, UL 508
Contacts Type And Composition
1 NC
Positive Opening
with IEC 60947-5-2
[Uimp] Rated Impulse Withstand Voltage
2.5 kV IEC 60947-1
[Ie] Rated Operational Current
3 A 240 V, AC-15, A600-Q600 NEMA || 0.55 A 125 V, DC-13, A600-Q600 NEMA
Connections - Terminals
screw clamp terminals, 1 x 0.22 to 2 x 2.5 mm² IEC 60947-1, screw-clamp terminals
Shape Of Screw Head
cross slotted
Rated Breaking Capacity
3 kA 240 V AC-15, 720 VA || 6 kA 120 V AC-15, 720 VA || 1.2 kA 600 V AC-15, 720 VA || 1.5 kA 480 V AC-15, 720 VA || 0.1 kA 600 V DC-13 || 0.27 kA 250 V DC-13 || 0.55 kA 125 V DC-13
Ambient Air Temperature For Storage
-40-70°C
Vibration Resistance
7 gn 2-500 Hz)IEC 60068-2-6
Contact Operation
late-break
Short-Circuit Protection
10 A cartridge fuse IEC 60947-5-1
[Us] Rated Supply Voltage
0 to 600 V
Product Or Component Type
contact block
[Icm] Rated Short-Circuit Making Capacity
12 kA 600 V AC-15, 7200 VA || 15 kA 480 V AC-15, 7200 VA || 30 kA 240 V AC-15, 7200 VA || 60 kA 120 V AC-15, 7200 VA || 0.55 kA 125 V DC-13 || 0.1 kA 600 V DC-13 || 0.27 kA 250 V DC-13
[Ui] Rated Insulation Voltage
250 V 3)IEC 60947-1
Contacts Material
silver alloy contacts
Tightening Torque
0.8-0.8 N.m IEC 60947-1
[Ith] Conventional Free Air Thermal Current
10 A
Ambient Air Temperature For Operation
-25-70°C
Shock Resistance
50 gn IEC 60068-2-27
Ip Degree Of Protection
IP20 IEC 60529
Electrical Shock Protection Class
class II IEC 61140
Product Certifications
NEMA || UL 508
Terminals Description Iso N°1
(3-4)NO_CL
Terminals Description Iso N°1
(3-4)NO_CL
Terminal Connection Type
Screw Clamp Terminals
DC Contact Rating
Not Applicable
Includes Mounting Block
Not Applicable
Compatible with Series
9001K, 9001SK
Manufacturer Warranty Length
18 mo
Compatible Operator
Push Button
AC Contact Rating
1.2 A @600 V, 1.5 A @ 480 V, 3 A @ 240 V, 6 A @ 120 V
Switch Action
Momentary/Late Break
Country of Origin (subject to change)
Mexico