Item - Relay
Prewired Relay
Application - Prewired Relay
Pilot Duty
Coil Volts
10 to 30V AC/DC, 120V AC
AC Contact Rating - Relay
10A @ 277V
DC Contact Rating - Relay
10A @ 28V
Mounting - Relay
1/2 in Nipple, Surface
Power Consumption - Relay
0.6W, 3.4VA
Contact Amp Rating (Resistive)
10A @ 277VAC, 10A @ 28VDC
Standards
CE Certified, RoHS Compliant, UL 508, UL Listed
Body Height - Relay
1.7 in
Features
1/2 in NPT Nipple, 16 in Wire Leads, LED Indicator, Pilot Duty
Hz - Electrical
50 Hz, 60 Hz
Overall Height - Relay
1.7 in
Contact Material
Gold Flashed Silver Cadmium Oxide
Item
Enclosed Pre-Wired Relay
Horsepower @ 240V AC
1/6 hp
Contact Rating (AC)
10 A @ 277V
Mechanical Operating Durability
10,000,000
Status Indicator
LED Indicator
Contact Rating (DC)
10 A @ 28V
For Use With
Exhaust Fans, Motors, Vacuums
Input Voltage
10 to 30V AC, 120V AC/DC
Operating Current
10 A at 10 to 30V AC/DC, 10 A at 120V AC
Horsepower @ 120V AC
1/6 hp
Minimum Operating Temperature
-30 Degrees F
Power Consumption
0.6 W, 3.4 VA
Maximum Operating Temperature
140 Degrees F
No. of Relays u0026 Contact Type
One (1) SPDT Continuous Duty Coil
Relay Status
LED On - Activated
Coil Current
33 mA @ 10 Vac 35 mA @ 12 Vac 46 mA @ 24 Vac 55 mA @ 30 Vac 28 mA @ 120 Vac (RIBU1C) 13 mA @ 10 Vdc 15 mA @ 12 Vdc 18 mA @ 24 Vdc 20 mA @ 30 Vdc
Operating Temperature
-30 to 140° F
Expected Relay Life
10 million cycles minimum mechanical
Coil Voltage Input
10-30 Vac/dc ; 120 Vac ; 50-60 Hz (RIBU1C) Drop Out - 2.1 Vac / 2.8 Vdc Pull In - 9 Vac / 10 Vdc
Contact Ratings
10 Amp Resistive @ 277 Vac 10 Amp Resistive @ 28 Vdc 480 VA Pilot Duty @ 240-277 Vac 480 VA Ballast @ 277 Vac Not rated for Electronic Ballast 600 Watt Tungsten @ 120 Vac (N/O) 240 Watt Tungsten @ 120 Vac (N/C) 1/3 HP @ 120-240 Vac (N/O) 1/6 HP @ 120-240 Vac (N/C) 1/4 HP @ 277 Vac (N/O) 1/8 HP @ 277 Vac (N/C)
Housing Rating
NEMA 4X housing
Approvals
UL Listed, C-UL, CE (All models), UL508
Humidity Range
5 to 95% (noncondensing)
Country of Origin (subject to change)
United States