Item
Enclosed Relay,20A,SPST,Override
Operating Temperature
-30 to 140° F
Housing Rating
UL Accepted for Use in Plenum, NEMA 1
Relay Status
LED On - Activated
Humidity Range
5 to 95% (noncondensing)
Approvals
UL Listed, UL916, C-UL, CE
Power Input
42 mA @ 120 Vac (RIB01SBDC)
No. of Relays u0026 Contact Type
One (1) SPST Continuous Duty Coil
Expected Relay Life
10 million cycles minimum mechanical
Contact Ratings
20 Amp Resistive @ 277 Vac 1110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 20 Amp Ballast @ 277 Vac (N/O) 10 Amp Ballast @ 277 Vac (N/C) Not rated for Electronic Ballast 10 Amp Tungsten @ 120 Vac (N/O) 240 Watt Tungsten @ 120 Vac (N/C) 2 HP @ 277 Vac 1 HP @ 120 Vac
Country of Origin (subject to change)
United States