Item
Enclosed Relay/Current Switch,Adj.,10A
Type
Internal w/ contact status
Housing Rating
UL Accepted for Use in Plenum, NEMA 1
Coil Current
33 mA @ 10 Vac 35 mA @ 12 Vac 46 mA @ 24 Vac 55 mA @ 30 Vac 13 mA @ 10 Vdc 15 mA @ 12 Vdc 18 mA @ 24 Vdc 20 mA @ 30 Vdc
Sensor Output
Solid State Contact 30 Vac/dc, 0.4 Amp
Contact Ratings
10 Amp Resistive @ 277 Vac 480 VA Pilot Duty @ 277 Vac 480 VA Ballast @ 277 Vac Not rated for Electronic Ballast 600 Watt Tungsten @ 120 Vac (N/O) 240 Watt Tungsten @ 120 Vac (N/C) 1/3 HP @ 120-240 Vac (N/O) 1/6 HP @ 120-240 Vac (N/C) 1/4 HP @ 277 Vac (N/O) 1/8 HP @ 277 Vac (N/C)
Approvals
UL Listed, UL916, C-UL, CE
Humidity Range
5 to 95% (noncondensing)
Coil Voltage Input
10-30 Vac/dc ; 50-60 Hz Drop Out - 2.1 Vac / 2.8 Vdc Pull In - 9 Vac / 10 Vdc
Relay Status
Red LED On - Activated
Operating Temperature
-30 to 140° F
Expected Relay Life
10 million cycles minimum mechanical
No. of Relays u0026 Contact Type
One (1) SPST Continuous Duty Coil
Country of Origin (subject to change)
United States