Type
Toroid Sensor MA120 TA 120mm (47 in)
For Use With
TeSys T Motor Management System
Mounting
Fixed Cables, Fixed Plain Backplate, Fixed Profiled Sheet Metal, Fixed Slotted Backplate, Din Rail
Application
Equipment Monitoring and Control
Rated Short-Time Withstand Current
85 kA at 0.5 s
Rated Insulation Volts
1000V
Connection Type
Screw Connection
Impulse Withstand Voltage
12 kV
Operating Temp. Range
-35 to 70°C
Features
Mercury Free; Overvoltage Category IV; Pollution Degree level 3 IEC 60664-1
Storage Temp. Range
-55 to 85°C
Compatible Series
RH10M, RH10P, RH197M, RH197P, RH21M, RH21P, RH68M, RH86M, RH86P, RH99M, RH99P, RHU, RHUs, RMH
Product Type
Closed Toroid
Cable Outer Diameter
2.36 in (60 mm) 0.37 in² (240 mm²)
Rated Short Time Withstand Current
85 kA 0.5 s
Diameter
Inner 4.72 in (120 mm)
Range Compatibility
VigiPacT RH10M residual current protection relay; VigiPacT RH10P residual current protection relay; VigiPacT RH21M residual current protection relay; VigiPacT RH21P residual current protection relay; VigiPacT RH68M residual current protection relay; VigiPacT RH86M residual current protection relay; VigiPacT RH86P residual current protection relay; VigiPacT RH99M residual current protection relay; VigiPacT RH99P residual current protection relay; VigiPacT RH197M residual current protection relay; VigiPacT RH197P residual current protection relay; VigiPacT RHU residual current protection relay; VigiPacT RHUs residual current protection relay; VigiPacT RMH residual current protection relay
Rated Insulation Voltage
1000 V
Mounting Mode
Fixed cables; Fixed plain backplate; Fixed profiled sheet metal; Fixed slotted backplate; Clip-on DIN rail)
Residual Short-Circuit Withstand Current
85 kA / 0.5 s IEC 60947-2
Current Sensor Type
A type closed toroid
Product Or Component Type
Earth leakage current sensor
Ambient Air Temperature For Storage
-67 to 185°F (-55 to 85°C)
Rated Operational Current
250 A
Ambient Air Temperature For Operation
-31 to 158°F (-35 to 70°C)
Pollution Degree
Level 3 IEC 60664-1
Connections - Terminals
Screw connection 0.00 in² (0.22 mm²)
Environmental Characteristic
Exposure to damp heat not in service 25 to 55°C, RH 95%) 28 cycles IEC 60068-2-30; Salt mistKb/2 IEC 60068-2-52; Exposure to damp heat in servicecategory C2 48 hours IEC 60068-2-56
IP Degree Of Protection
Connectors IP20; IP30
Country of Origin (subject to change)
France