Item
IEC Magnetic Contactor
Full Load Amps-Inductive
9 A
Full Load Amps-Resistive
20 A
HP @ 1 Phase - 120V
1/2 hp
HP @ 3 Phase - 575V
7 1/2 hp
Enclosure NEMA Rating
No Enclosure
Aux. Contact Configuration
1NO/1NC
Standards
BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed
Auxiliary Contact Form
1NO/1NC
Includes
Electrical Interlock
Vibration Resistance
4 G (Contactor Closed), 2 G (Contactor Open)
Tightening Torque
1.7 Nm (Control Circuit), 1.7 to 2.5 Nm (Power Circuit)
Rated Breaking Capacity
250 A @ 440V
Thermal Amperage
10 A (at 60°C Signalling Circuit), 25 A (at 60°C Power Circuit)
Application
Motor Control, Resistive Load
Insulation Resistance Range
Greater Than 10 MOhms (Signalling Circuit)
Shock Resistance
15 G for 11 ms (Contactor Closed), 10 G for 11 ms (Contactor Open)
Operating Time
12 to 22 ms (Closing), 4 to 19 ms (Opening)
Impulse Withstand Voltage
6 kV
Features
Without Built-In Suppressor Module; Preassembled with Reversing Power Busbar
Signalling Circuit Frequency
25 to 400 Hz
Fuse Amps
25 A (Type 1 Power Circuit), 20 A (Type 2 Power Circuit), 10 A (Signalling Circuit)
Rated Voltage
690V AC, 300V DC
Mechanical Durability
15 Mcycles
Includes Protective Cover
Yes
Rated Making Capacity
250 A @ 440V (Power Circuit), 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit)
Control Circuit Voltage Limits
Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz); Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz)
Rated Short-Time Withstand Current
30 A (at 40°C for 10 min Power Circuit), 61 A (at 40°C for 1 min Power Circuit), 105 A (at 40°C for 10 s Power Circuit), 210 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit)
Working Height
Up to 9842.52 ft
Electrical Durability
0.6 Mcycles (25 A, AC-1, Less than 440 V); 2 Mcycles (9 A, AC-3, Less than 440 V)
Environmental Attributes
Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3
Operating Speed
3600 cycles per hr
Max. Operating Watts
2.2 kW (at 220 to 230V AC 50 Hz), 4 kW (at 380 to 400V AC 50 Hz), 4 kW (at 415 to 440V AC 50 Hz), 5.5 kW (at 500V AC 50 Hz), 5.5 kW (at 660 to 690V AC 50 Hz)
Rated Insulation Volts
600/690V
Switching Voltage
17 V (Signalling Circuit)
Overvoltage Category
CAT III
Hold VA
7.5 VA (at 60 Hz 20°C), 7 VA (at 50 Hz 20°C)
Electrical Connection
Screw Clamp Terminals
Switching Current
5 mA (Signalling Circuit)
Resistance Properties
Fire Resistant, Insulation Resistant
Number of Auxillary Contacts
2
NEMA Enclosure Material
Not Applicable
Electrical Operating Durability
2,000,000, 600,000
Maximum Operating Temperature
140 Degrees F
Reversing Capability
Reversing
Horsepower @ Three Phase - 240V AC
2 hp
Horsepower @ Single Phase - 120V AC
1/2 hp
Horsepower @ Three Phase - 600V AC
7 1/2 hp
Mechanical Operating Durability
15,000,000
Maximum Voltage Rating
690V AC
Number of Normally Open Main Contacts
3
Full Load Current - Resistive
20 A
NEMA Enclosure Rating
No Enclosure
Minimum Operating Temperature
-40 Degrees F
Horsepower @ Three Phase - 480V AC
5 hp
Full Load Current - Inductive
9 A
Embedded Surge Suppressor
No
Terminal Connection Type
Screw Clamp Terminals
Horsepower @ Single Phase - 240V AC
1 hp
Mounting Style
DIN Rail, Plate
Horsepower @ Three Phase - 208V AC
2 hp
Includes Auxiliary Contacts
Yes
Country of Origin (subject to change)
Indonesia