Item
IEC Magnetic Contactor
Full Load Amps-Inductive
52 A
Full Load Amps-Resistive
70 A
Enclosure NEMA Rating
No Enclosure
Aux. Contact Configuration
1NO/1NC
Frame / Series / Class / Code
S2
Standards
REACH Art 33, WEEE (2012/19/EU)
Auxiliary Contact Form
1NO/1NC
Watts Loss
4W (Current Dependent); 17.2W (Current Independent)
Max. Operating Watts
22 kW (at 400V, AC-3), 46 kW (at 400V, AC-1)
Electrical Connection
Screws
Terminal Connection Type
Screw Terminals
NEMA Enclosure Rating
No Enclosure
Full Load Current - Inductive
51 A
Horsepower @ Single Phase - 120V AC
3 hp
Maximum Operating Temperature
140 Degrees F
Horsepower @ Three Phase - 480V AC
40 hp
Maximum Voltage Rating
690V AC
Horsepower @ Three Phase - 600V AC
50 hp
Mounting Hole Distance - Height
3.84 in
Horsepower @ Three Phase - 208V AC
15 hp
Horsepower @ Three Phase - 240V AC
15 hp
Mounting Hole Diameter
0.2 in
Mechanical Operating Durability
10,000,000
Number of Auxillary Contacts
2
Number of Normally Open Main Contacts
3
Mounting Style
DIN Rail, Surface
NEMA Enclosure Material
Not Applicable
Reversing Capability
Non-Reversing
Full Load Current - Resistive
70 A
Minimum Operating Temperature
-13 Degrees F
Embedded Surge Suppressor
No
Mounting Hole Distance - Width
1.77 in
Includes Auxiliary Contacts
Yes
Response Time
10 to 18 msec (AC Operation Opening Delay Operating Times for 0.8 ... 1.1 x Us1), 10 to 18 msec (AC Operation Opening Delay Operating Times for 1.0 x Us1), 10 to 80 msec (AC Operation Closing Delay Operating Times for 0.8 ... 1.1 x Us1), 12 to 22 msec (AC Operation Closing Delay Operating Times for 1.0 x Us1)
Horsepower @ Single Phase - 240V AC
10 hp
Country of Origin (subject to change)
Germany