Full Load Amps-Inductive | 40 A |
Item | IEC Magnetic Contactor |
Full Load Amps-Resistive | 60 A |
Action | Non-Reversing |
Number of Poles | 3 |
Coil Volts | 240 V AC |
Reversing | No |
HP @ 1 Phase - 120V | 3 hp |
HP @ 1 Phase - 230V | 5 |
HP @ 1 Phase - 240V | 5 hp |
Height | 2.17 in |
Width | 2.17 in |
HP @ 3 Phase - 208V | 10 hp |
HP @ 3 Phase - 575V | 30 hp |
HP @ 3 Phase - 240V | 10 hp |
Depth | 4.61 in |
Enclosure NEMA Rating | No Enclosure |
HP @ 3 Phase - 480V | 30 hp |
Aux. Contact Configuration | 1NO/1NC |
Hz | 50/60 |
Auxiliary Contact Form | 1NO/1NC |
Frame / Series / Class / Code | TeSys |
Standards | CCC, CSA, CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, GOST, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508, UL Listed |
NEMA Size | Not Applicable |
Includes | Everlink Power Connections |
Series | TeSys Deca |
Operating Speed | 3600 cycles per hr |
Switching Current | 5 mA (Signalling Circuit) |
Rated Short-Time Withstand Current | 320 A (at 40°C for 10 s Power Circuit), 720 A (at 40°C for 1 s Power Circuit), 72 A (at 40°C for 10 min Power Circuit), 165 A (at 40°C for 1 min Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit) |
IP Rating | IP20 |
Operating Time | 4 to 19 ms (Opening), 12 to 26 ms (Closing) |
Fire Rating | UL 94 V1 |
Non-Overlap Time | 1.5 ms |
Vibration Resistance | 4 G (Contactor Closed), 2 G (Contactor Open) |
Features | Without Built-In Suppressor Module |
Control Circuit Voltage Limits | Drop-Out AC: 0.3 to 0.6 Uc (at -40 to 70°C 50/60 Hz), Operational AC: 0.8 to 1.1 Uc (at -40 to 60°C 50 Hz), 0.85 to 1.1 Uc (at -40 to 60°C 60 Hz), 1 to 1.1 Uc (at 60 to 70°C 50/60 Hz) |
Signalling Circuit Frequency | 25 to 400 Hz |
Application | Motor Control, Resistive Load |
Rated Insulation Volts | 600/690V |
Thermal Amperage | 10 A (at 60°C Signalling Circuit), 60 A (at 60°C Power Circuit) |
Switching Voltage | 17 V (Signalling Circuit) |
Net Weight | 0.85 kg |
Inrush VA | 140 VA (at 60 Hz 20°C), 160 VA (at 50 Hz 20°C) |
Overvoltage Category | CAT III |
Environmental Attributes | Mercury Free, PVC Free, Toxic Heavy Metal Free, Pollution Degree 3 |
Rated Making Capacity | 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 800 A @ 440V (Power Circuit) |
Electrical Durability | 1.4 Mcycles (60 A, AC-1, Less than 440 V), 1.5 Mcycles (40 A, AC-3, Less than 440 V), 1.5 Mcycles (40 A, AC-3e, Less than 440 V) |
Insulation Resistance Range | Greater Than 10 MOhms (Signalling Circuit) |
Includes Protective Cover | Yes |
Max. Operating Watts | 18.5 kW (at 380 to 400V AC 50/60 Hz AC-3), 11 kW (at 220 to 230V AC 50/60 Hz AC-3), 22 kW (at 415 to 440V AC 50/60 Hz AC-3), 22 kW (at 500V AC 50/60 Hz AC-3), 30 kW (at 660 to 690V AC 50/60 Hz AC-3), 9 kW (at 400V AC 50/60 Hz AC-4), 18.5 kW (at 380 to 400V AC 50/60 Hz AC-3e), 11 kW (at 220 to 230V AC 50/60 Hz AC-3e), 22 kW (at 415 to 440V AC 50/60 Hz AC-3e), 22 kW (at 500V AC 50/60 Hz AC-3e), 30 kW (at 660 to 690V AC 50/60 Hz AC-3e) |
Tightening Torque | 1.7 Nm (Control Circuit), 2.5 to 8 Nm (Power Circuit) |
Fuse Amps | 10 A (Signalling Circuit), 80 A (Type 1 Power Circuit), 80 A (Type 2 Power Circuit) |
Mounts On | Plate, Rail |
Electrical Connection | Screw Clamp Terminals |
Shock Resistance | 10 G for 11 ms (Contactor Open), 15 G for 11 ms (Contactor Closed) |
Impedance | 1.5 mOhm |
Working Height | Up to 9842.52 ft |
Mechanical Durability | 6 Mcycles |
Max. Temperature | 850°C |
Hold VA | 13 VA (at 60 Hz 20°C), 15 VA (at 50 Hz 20°C) |
Watts Loss | 4 to 5W |
Impulse Withstand Voltage | 6 kV |
Rated Voltage | 690V AC, 300V DC |
Rated Breaking Capacity | 800 A @ 440V |
Includes Auxiliary Contacts | Yes |
NEMA Enclosure Rating | No Enclosure |
Full Load Current - Resistive | 60 A |
Overall Width | 2.17 in |
Overall Depth | 4.72 in |
Terminal Connection Type | Screw Clamp Terminals |
Maximum Voltage Rating | 690V AC |
NEMA Enclosure Material | Not Applicable |
Coil Voltage | 240V AC |
Reversing Capability | Non-Reversing |
Horsepower @ Single Phase - 120V AC | 3 hp |
Horsepower @ Three Phase - 240V AC | 10 hp |
Resistance Properties | Fire Resistant, Insulation Resistant |
Embedded Surge Suppressor | No |
Phase | Three |
Contactor Style | IEC |
Mechanical Operating Durability | 6,000,000 |
Maximum Operating Temperature | 140 Degrees F |
Number of Auxillary Contacts | 2 |
Horsepower @ Three Phase - 480V AC | 30 hp |
Horsepower @ Single Phase - 240V AC | 5 hp |
Mounting Style | DIN Rail, Plate |
Horsepower @ Three Phase - 208V AC | 10 hp |
Minimum Operating Temperature | -40 Degrees F |
Horsepower @ Three Phase - 600V AC | 30 hp |
Full Load Current - Inductive | 40 A |
Number of Normally Open Main Contacts | 3 |
Electrical Operating Durability | 1,400,000, 1,500,000 |
Overall Height | 4.8 in |
Frequency | 50/60 Hz |
Country of Origin (subject to change) | Multiple |
Package Quantity | 1 |
IEC Magnetic Contactor, 3 Poles, 240 V AC, 40 A, Reversing: No, SCHNEIDER ELECTRIC, Mfr# LC1D40AU7
$282,99
-$8.49 / ea
with subscription
Free shipping will be applied on orders over $50
IEC Magnetic Contactor, Auxiliary Contact Form 1NO/1NC, NEMA Enclosure Rating No Enclosure, NEMA Size Not Applicable, Coil Voltage 240V AC, Number of Poles 3, Full Load Current - Inductive 40 A, Full Load Current - Resistive 60 A, Reversing Capability Non-Reversing, Overall Height 4.8 in, Overall Width 2.17 in, Terminal Connection Type Screw Clamp Terminals, Mounting Style DIN Rail, Plate, Series TeSys Deca, Number of Auxillary Contacts 2, Contactor Style IEC
9999 in stock
Must order in multiples of 1
Subtotal:
$282.99
You must be logged in to post a review.