Enclosure NEMA Rating
7, 9
Number of Required Thermals
1
Standards
CSA LR25490, E42243 CCN NLRV, UL Listed
Description/Special Features
Handle Guard Lock-Off
Thermal Overload Type
melting alloy
Product Or Component Type
Single Unit Manual Starter
Control Type
toggle switch (with lock-off)
Motor Starter Type
non reversing
Product Certifications
UL listed file E42243 CCN NLRV || CSA LR25490 class 3211 05
Maximum Horse Power Rating
1 hp 115 V AC || 1 hp 277 V AC || 0.75 hp 115 V DC || 0.75 hp 230 V DC || 2 hp 230 V AC
Local Signalling
no indicator
Awg Gauge
AWG 14...AWG 12 copper
Cable Entry
0.75 NPT (bottom)
Electrical Connection
screw clamp terminals
[Ue] Rated Operational Voltage
277 V AC || 230 V DC
Nema Degree Of Protection
NEMA 3R/7/9 Cast Aluminium standard size
Minimum Overload Relay Current Setting
Not Applicable
Terminal Connection Type
Screw Terminals
Overload Protection Type
Thermal
Horsepower @ 230V DC
3/4 hp
Maximum Overload Relay Current Setting
Not Applicable
Status Indicator
No Indicator
Horsepower @ 115V DC
3/4 hp
Horsepower @ Single Phase - 240V AC
2 hp
Horsepower @ Single Phase - 120V AC
1 hp
Hazardous Location Specification
Class I, Div 1 and 2, Group B, C, D, Class II, Div 1 and 2, Group E, F, G
Maximum Voltage Rating
277V AC/230V DC
Series
Class 2510 F Series
Country of Origin (subject to change)
Mexico