| Property | Value |
|---|---|
| Operator | Selector Switch |
| NEMA Size | Not Applicable |
| Enclosure NEMA Rating | No Enclosure |
| Depth | 3.83 in |
| Overload Relay Amp Setting | 1.6 to 2.5A |
| Height | 3.5 in |
| Item | Manual Motor Starter |
| Width | 1.75 in |
| Number of Poles | 3 |
| HP @ 3 Phase - 480V | 1 hp |
| Max. Voltage | 600V AC |
| HP @ 3 Phase - 240V | 1/2 hp |
| Pilot Light | Yes |
| HP @ 3 Phase - 460-575V | 1/1-1/2 |
| HP @ 3 Phase - 575V | 1 1/2 hp |
| Description/Special Features | Reliable Overload Protection |
| HP @ 3 Phase - 208V | 1/2 hp |
| Phase Loss Sensitivity | Yes |
| HP @ 1 Phase - 230V | 1/6 hp |
| Standards | ATEX Compliant, BV, CCC, CSA, DNV-GL, EAC, EN/IEC 60947-2, EN/IEC 60947-4, LROS, RINA, UKCA, UL Listed |
| Product Certifications | CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA |
| Fixing Mode | 35 mm symmetrical DIN rail clipped || panel screwed with 2 x M4 screws) |
| Ambient Air Temperature For Operation | -20-60ΓΒ°C |
| Phase Failure Sensitivity | yes IEC 60947-4-1 |
| Trip Unit Technology | thermal-magnetic |
| Product Or Component Type | motor circuit breaker |
| Ambient Air Temperature For Storage | -40-80ΓΒ°C |
| Mechanical Durability | 100000 cycles |
| Thermal Protection Adjustment Range | 1.6-2.5 A IEC 60947-4-1 |
| Breaking Capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 8 kA Icu 690 V AC 50/60 Hz IEC 60947-2 |
| Line Rated Current | 2.5 A |
| Tightening Torque | 1.7 N.m screw clamp terminal |
| Operating Altitude | 6561.68 ft (2000 m) |
| Product Name | TeSys GV2 || TeSys Deca |
| Electrical Durability | 100000 cycles AC-3 415 V In |
| Rated Duty | continuous IEC 60947-4-1 |
| [Ue] Rated Operational Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| Range | TeSys Deca |
| [Ith] Conventional Free Air Thermal Current | 2.5 A IEC 60947-4-1 |
| Mechanical Robustness | shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz |
| Network Type | AC |
| Color | dark grey |
| Magnetic Tripping Current | 33.5-33.5 A |
| Power Dissipation Per Pole | 2.5 W |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV IEC 60947-2 |
| Network Frequency | 50/60 Hz IEC 60947-4-1 |
| Control Type | rotary handle |
| Motor Power Kw | 0.75-0.75 kW 400/415 V AC 50/60 Hz || 1.1-1.1 kW 500 V AC 50/60 Hz || 1.5-1.5 kW 690 V AC 50/60 Hz |
| Ip Degree Of Protection | IP20 IEC 60529 |
| Suitability For Isolation | yes IEC 60947-1ΓΒ§ 7-1-6 |
| Fire Resistance | 960ΓΒ°C IEC 60695-2-11 |
| Climatic Withstand | IACS E10 |
| Ik Degree Of Protection | IK04 |
| Poles Description | 3P |
| Device Short Name | GV2P |
| [Ui] Rated Insulation Voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| Device Application | motor protection |
| Utilisation Category | category A IEC 60947-2 || AC-3 IEC 60947-4-1 |
| [Ics] Rated Service Short-Circuit Breaking Capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 690 V AC 50/60 Hz IEC 60947-2 |
| Maximum Overload Relay Current Setting | 2.5 A |
| NEMA Enclosure Rating | No Enclosure |
| Horsepower @ Three Phase - 208V AC | 1/2 hp |
| Electrical Operating Durability | 100,000 |
| Horsepower @ Three Phase - 600V AC | 1 1/2 hp |
| Horsepower @ Single Phase - 240V AC | 1/6 hp |
| Status Indicator | LED Indicator |
| Minimum Overload Relay Current Setting | 1.6 A |
| Resistance Properties | Fire Resistant |
| Overload Protection Type | Thermal |
| Overall Height | 3.5 in |
| Horsepower @ Three Phase - 240V AC | 1/2 hp |
| IP Rating | IP20 |
| Phase | Three |
| Series | TeSys Deca |
| Maximum Operating Temperature | 140 Degrees F |
| Overall Width | 1.77 in |
| Minimum Operating Temperature | -4 Degrees F |
| Terminal Connection Type | Screw Clamp Terminals |
| Horsepower @ Three Phase - 480V AC | 1 hp |
| Mechanical Operating Durability | 100,000 |
| Overall Depth | 3.82 in |
| Includes Pilot Light | No |
| Maximum Voltage Rating | 600V AC |
| Starter Style | IEC |
| Frequency | 50/60 Hz |
| Current AC | 2.5 A |
| Country of Origin (subject to change) | Thailand |
| Package Quantity | 1 |
Manual Motor Starter, Knob, 1.6 to 2.5A, 3P, Square D, Mfr#: GV2P07
$232.99
Free shipping will be applied on orders over $50
TeSys Deca Manual Starter and Protector, thermal magnetic circuit protector, rotary handle, 1.6 to 2.5 A, screw clamp
9999 in stock
Subtotal:
$232.99
You must be logged in to post a review.
Reviews
There are no reviews yet.