Item
Manual Starter 600Vac 10Amp Iec
Standards
EN/IEC 60947-2 || EN/IEC 60947-4-1
Utilisation Category
category A IEC 60947-2 || AC-3 IEC 60947-4-1
Product Or Component Type
motor circuit breaker
Phase Failure Sensitivity
yes IEC 60947-4-1
Ip Degree Of Protection
IP20 IEC 60529
Suitability For Isolation
yes IEC 60947-1§ 7-1-6
Fire Resistance
960°C IEC 60695-2-11
Climatic Withstand
IACS E10
Electrical Durability
100000 cycles AC-3 415 V In
Trip Unit Technology
thermal-magnetic
Mechanical Durability
100000 cycles
Power Dissipation Per Pole
2.5 W
Product Name
TeSys GV2 || TeSys Deca
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Breaking Capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Ik Degree Of Protection
IK04
Motor Power Kw
3-3 kW 400/415 V AC 50/60 Hz || 4-4 kW 400/415 V AC 50/60 Hz || 4-4 kW 500 V AC 50/60 Hz || 5.5-5.5 kW 500 V AC 50/60 Hz
Mechanical Robustness
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5 to 150 Hz
Rated Duty
continuous IEC 60947-4-1
Ambient Air Temperature For Operation
-20-60°C
Ambient Air Temperature For Storage
-40-80°C
[Ith] Conventional Free Air Thermal Current
10 A IEC 60947-4-1
[Ics] Rated Service Short-Circuit Breaking Capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
Fixing Mode
35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-2
Product Certifications
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
Magnetic Tripping Current
138-138 A
Device Application
motor protection
[Ui] Rated Insulation Voltage
690 V AC 50/60 Hz IEC 60947-2
Thermal Protection Adjustment Range
6-10 A IEC 60947-4-1
Operating Altitude
6561.68 ft (2000 m)
Network Frequency
50/60 Hz IEC 60947-4-1
Rated Service Short-Circuit Breaking Capacity
100% 230/240 V AC 50/60 Hz IEC 60947-2; 100% 400/415 V AC 50/60 Hz IEC 60947-2; 100% 440 V AC 50/60 Hz IEC 60947-2; 100% 500 V AC 50/60 Hz IEC 60947-2; 75% 690 V AC 50/60 Hz IEC 60947-2
Country of Origin (subject to change)
France