Item
Molded Case Circuit Breaker
Circuit Breaker Type
Standard
Circuit Breaker Actuator
Toggle
Circuit Breaker Mounting Style
I-Line
Max. AIR Rating
65kA at 240V AC
Trip Type
Thermal Magnetic
Instantaneous Trip
Adjustable
Terminal Connection
I-Line, Lug
DC Voltage Rating
250/500V DC
For Use With
I Line Panelboards
High Amp Trip Setting
1,500 A
Low Amp Trip Setting
750 A
Standards
BS, CCC, CE Marked, CEI, CSA Certified, Federal Specification W-C-375B/GEN, HACR, HID, IEC, NEMA, NMX, NOM, SWD, UL Listed, UNE, UTE, VDE
Interrupt Rating
65 kA at 220/240V AC, 35 kA at 380/440/415/480V AC, 18 kA at 500/525/600V AC, 20 kA at 250/500V DC
Features
Mercury Free; PVC Free
Application
HACR rated Applications; Distribution
Magnetic Tripping Current
1750 A
Ambient Air Temperature For Storage
-58 to 185°F (-50 to 85°C)
Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Operating Altitude
Less than 6561.68 ft (2000 m) without derating; 5000 m with derating
Number Of Slots
2 auxiliary switch OF plug-in); 1 alarm switch SD plug-in); 1 overcurrent trip switch SDE plug-in); 1 voltage release MN or MX plug-in)
Utilisation Category
Category A
Suitability For Isolation
Yes IEC 60947-2
Rated Insulation Voltage
750 V IEC 60947-2
Rated Operational Voltage
600 V AC 50/60 Hz IEC 60947-3
Long Time Pick-Up Adjustment Range
0.25 to 1 x In
Circuit Breaker Application
HACR rated
Local Signalling
Switched off (OFF) 1 trip indicator green)
Ambient Air Temperature For Operation
28 to 158°F (-2 to 70°C)
Communication Interface
Modbus; Ethernet
Continuous Current Rating
0.8
Product Certifications
UL; CSA; NOM
Tightening Torque
221.27 lbf.in (25 N.m) 0.04 to 0.15 in² (25 to 95 mm²) (AWG 4 to AWG 4/0)
AWG Gauge
AWG 4 to AWG 4/0 aluminium/copper terminal
Breaking Capacity
65 kA 240 V AC 50/60 Hz UL 489; 35 kA 480 V AC 50/60 Hz UL 489; 18 kA 600 V AC 50/60 Hz UL 489; 20 kA 250 V DC UL 489; 20 kA 500 V DC UL 489
Protection Type
Overload protection; Short-circuit protection
Terminal Identifier
AL175JD
Power Wire Stripping Length
0.98 in (25 mm)
Device Application
Distribution
Mounting Height
4.5 in (114.30 mm)
IP Degree Of Protection
Front cover IP40
Pollution Degree
3 IEC 60947-1
Network Frequency
50/60 Hz
Rated Service Breaking Capacity
65 kA 220/240 V AC 50/60 Hz IEC 60947-2; 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2; 18 kA 500/525 V AC 50/60 Hz IEC 60947-2; 20 kA 250 V DC IEC 60947-2; 20 kA 500 V DC IEC 60947-2
Country of Origin (subject to change)
United States