Item | IEC Overload Relay |
Item - Relay | IEC Style Overload Relay |
Use With - Contactors and Starters | Contactor DPE09-38 |
NEMA Size | Not Applicable |
Overload Relay Current Range | 1.00 to 1.70 A |
Trip Class - Overload | 10 |
Width | 45 mm |
Number of Poles | 3 |
Frame / Series / Class / Code | Class 10, Easy TeSys DPER |
Sensing Method | Thermal |
Reset Type - Relay | Manual |
Height | 66 mm |
Depth | 70 mm |
Body Height - Relay | 2.6 in |
Body Depth - Relay | 2.76 in |
Trip Class | 10 |
Features | 400 Hz Power Circuit IEC 60947-4-1, 5 A Signalling Circuit, 690 V AC |
Standards | cUL, EN/IEC 60947-4-1, EN/IEC 60947-5-1, REACH, RoHS, UL 60947-4-1, UL 60947-5-1 |
Body Width - Relay | 1.77 in |
Overall Height - Relay | 2.6 in |
Separate Mounting | Yes, Additional Items Needed |
Kit Required for Retrofit Mtg. | LAD9R1 |
Overall Height | 2.6 in |
Control Type | Red push-button stop || Blue push-button reset |
Range | Easy TeSys |
Ambient Air Temperature For Storage | -60-70°C |
Protection Type | BS fuse 5 A - control circuit || GB2 circuit breaker 5 A - control circuit || gG fuse 5 A - control circuit |
Surge Withstand | 6 kV IEC 60801-5 |
[Ith] Conventional Free Air Thermal Current | 5 A signalling circuit |
Product Or Component Type | thermal overload relay |
Tripping Threshold | 1.14 +/- 0.06 Ir IEC 60947-4-1 |
[Ui] Rated Insulation Voltage | power circuit 600 V cUL || power circuit 690 V IEC 60947-4-1 |
Product Name | Easy TeSys DPER |
Network Type | DC || AC |
Phase Failure Sensitivity | tripping current 130 % of Ir on two phase, the last one at 0 |
Thermal Overload Class | class 10 IEC 60947-4-1 |
Mounting Support | separate, with specific accessories || under contactor |
Relay Application | overload protection |
Protective Treatment | TH IEC 60068 |
Auxiliary Contact Composition | 1 NO + 1 NC |
Tightening Torque | control circuit 1.7 N.m screw clamp terminals || power circuit 1.7 N.m screw clamp terminals |
Product Certifications | cUL |
Product Compatibility | contactor DPE09-38 |
Thermal Protection Adjustment Range | 1-1.7 A |
Dielectric Strength | 1.89 kV 50 Hz IEC 60947-1 |
Permissible Current | 3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit |
Connections - Terminals | control circuit screw clamp terminals 2 1-2.5 mm? flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm? flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm? solid without cable end || power circuit screw clamp terminals 1 1.5-6 mm? flexible without cable end || power circuit screw clamp terminals 1 1-4 mm? flexible with cable end || power circuit screw clamp terminals 1 1-6 mm? solid without cable end |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
Ambient Air Temperature For Operation | -20-60°C without derating IEC 60947-4-1 |
Temperature Compensation | -20-60°C |
Device Short Name | DPER |
Vibration Resistance | 6 gn on plate IEC 60068-2-6 |
Shock Resistance | 15 gn 11 ms IEC 60068-2-7 |
[Ue] Rated Operational Voltage | 690 V AC 0 to 400 Hz power circuit IEC 60947-4-1 |
Network Frequency | 0 to 400 Hz |
Ip Degree Of Protection | IP20 conforming to IEC 60529 |
Maximum Overload Relay Current Setting | 1.6 A |
Maximum Operating Temperature | 140 Degrees F |
Relay Style | IEC |
Mounting Style | Separately Mounted |
Maximum Voltage Rating | 690V AC |
Terminal Connection Type | Screw Clamp Terminals |
IP Rating | IP20 |
Phase | Three |
Body Depth | 2.76 in |
Body Height | 2.6 in |
Reset Type | Auto, Manual |
Body Width | 1.77 in |
Compatible with Series | Easy TeSys |
Overload Protection Type | Thermal |
Minimum Operating Temperature | -4 Degrees F |
Auxiliary Contact Form | 1NO/1NC |
Minimum Overload Relay Current Setting | 1 A |
Country of Origin (subject to change) | France |
Package Quantity | 1 |
OverloadRelay, IEC, Thermal, Auto/Manual, SCHNEIDER ELECTRIC, Mfr# DPER06
$25,25
Free shipping will be applied on orders over $50
IEC Overload Relay, Auxiliary Contact Form 1NO/1NC, Maximum Overload Relay Current Setting 1.6 A, Minimum Overload Relay Current Setting 1 A, Trip Class 10, Maximum Voltage Rating 690V AC, NEMA Size Not Applicable, Number of Poles 3, Reset Type Auto, Manual, Mounting Style Separately Mounted, Terminal Connection Type Screw Clamp Terminals, Compatible with Series Easy TeSys, Relay Style IEC, Overload Protection Type Thermal, Phase Three
9999 in stock
Must order in multiples of 1
Subtotal:
$25.25
You must be logged in to post a review.
Reviews
There are no reviews yet.