Item - Relay
IEC Style Overload Relay
Use With - Contactors and Starters
Mfr. Series LC1D09 to LC1D32 Contactors
Current Range
23.0 to 32.0A
Overload Relay Current Range
23 to 32A
Body Width - Relay
1.77 in
For Use With
TeSys D 9-32A, TeSys N Size 00-1 Contactors
Standards
CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, EN 50495, EN/IEC 60947-4-1, EN/IEC 60947-5-1, REACH, RoHS, UL 60947-4-1, UL 60947-5-1
Features
Single Phase Sensitivity; Differential
Overall Height - Relay
2.99 in
Body Height - Relay
2.99 in
Control Type
Red push-button stop || Blue push-button reset
Ip Degree Of Protection
IP20 conforming to IEC 60529
Network Frequency
0 to 400 Hz
[Ith] Conventional Free Air Thermal Current
5 A signalling circuit
Tightening Torque
control circuit 1.7 N.m screw clamp terminals || power circuit 2.5 N.m screw clamp terminals
Phase Failure Sensitivity
tripping current 130 % of Ir on two phase, the last one at 0
Thermal Protection Adjustment Range
23-32 A
Mounting Support
plate, with specific accessories || rail, with specific accessories || under contactor
Mechanical Robustness
shocks15 Gn for 11 ms IEC 60068-2-7 || vibrations3 GN IEC 60068-2-6
Auxiliary Contact Composition
1 NO + 1 NC
Climatic Withstand
IACS E10
[Uimp] Rated Impulse Withstand Voltage
6 kV
Ambient Air Temperature For Storage
-60-70°C
Thermal Overload Class
class 20 IEC 60947-4-1
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
Dielectric Strength
1.89 kV 50 Hz IEC 60947-1
Permissible Current
3 A 120 V AC-15 signalling circuit || 0.22 A 125 V DC-13 signalling circuit
Connections - Terminals
control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end || power circuit screw clamp terminals 1 1.5-10 mm² flexible without cable end || power circuit screw clamp terminals 1 1-6 mm² flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm² solid without cable end
Associated Fuse Rating
4 A gG signalling circuit || 4 A BS signalling circuit
[Ue] Rated Operational Voltage
690 V AC 0 to 400 Hz power circuit IEC 60947-4-1
Product Compatibility
LC1D32 || LC1D38 || LC1D25
Product Name
TeSys LRD || TeSys Deca
Product Or Component Type
differential thermal overload relay
Product Certifications
IEC || UL || CSA || EAC || ABS || ATEX INERIS || UKCA
Tripping Threshold
1.14 +/- 0.06 Ir IEC 60947-4-1
Ambient Air Temperature For Operation
-20-60°C without derating IEC 60947-4-1
Temperature Compensation
-20-60°C
Relay Application
motor protection
Minimum Operating Temperature
-4 Degrees F
Auxiliary Contact Form
1NO/1NC
Overload Protection Type
Thermal
Terminal Connection Type
Screw Clamp Terminals
Minimum Overload Relay Current Setting
23 A
Maximum Operating Temperature
140 Degrees F
Maximum Voltage Rating
690V AC
Compatible with Series
TeSys Deca
Maximum Overload Relay Current Setting
32 A
Mounting Style
Direct To Contactor
Includes Mounting Hardware
Not Applicable
Country of Origin (subject to change)
Thailand