Full Load Amps-Inductive
25 A
Full Load Amps-Resistive
40 A
HP @ 3 Phase - 240V
7 1/2 hp
Aux. Contact Configuration
1NO/1NC
Standards
REACH Art 33, WEEE (2012/19/EU)
Frame / Series / Class / Code
S0
Watts Loss
1.9W (Current Dependent); 10.5W (Current Independent)
Max. Operating Watts
11 kW (at 400V, AC-3), 23 kW (at 400V, AC-1)
Electrical Connection
Screws
Horsepower @ Three Phase - 600V AC
20 hp
Response Time
10 to 17 msec (AC Operation Closing Delay Operation Opening Delay Operating Times for 1.0 x Us1), 15 to 17.5 msec (DC Operation Opening Delay Operating Times For 0.8 ... 1.1 X Us1), 16 to 17 msec (DC Operation Opening Delay Operating Times for 1.0 x Us), 4 to 16 msec (AC Operation Opening Delay Operating Times for 0.8 ... 1.1 X Us1), 4 to 16 msec (AC Operation Opening Delay Operating Times for 1.0 x Us), 50 to 170 msec (DC Operation Closing Delay Operating Times for 0.8 ... 1.1 X Us1), 55 to 80 msec (DC Operation Closing Delay Operating Times for 1.0 x Us), 8 to 40 msec (AC Operation Closing Delay)
Mounting Hole Distance - Height
2.36 in
Mounting Hole Distance - Width
1.38 in
Number of Normally Open Main Contacts
3
NEMA Enclosure Rating
No Enclosure
Mechanical Operating Durability
10,000,000
Auxiliary Contact Form
1NO/1NC
Embedded Surge Suppressor
No
Maximum Operating Temperature
140 Degrees F
Full Load Current - Inductive
25 A
Full Load Current - Resistive
40 A
Horsepower @ Single Phase - 240V AC
3 hp
Number of Auxillary Contacts
2
Includes Auxiliary Contacts
Yes
Minimum Operating Temperature
-13 Degrees F
Horsepower @ Three Phase - 480V AC
15 hp
Maximum Voltage Rating
690V AC
Horsepower @ Single Phase - 120V AC
2 hp
Horsepower @ Three Phase - 208V AC
5 hp
Terminal Connection Type
Screw Terminals
Horsepower @ Three Phase - 240V AC
7 1/2 hp
Reversing Capability
Non-Reversing
Mounting Hole Diameter
0.19 in
Mounting Style
DIN Rail, Surface
Country of Origin (subject to change)