Item
Power Distribution Block 600V 420A
Primary Connections/Pole
1
Primary Wire Range (AWG)
AWG 4 to 600 kcmil (Copper or Aluminium)
Secondary Connection/Pole
1
Secondary Wire Range (AWG)
AWG 4 to 600 kcmil (Copper or Aluminium)
Power Distribution Block Design
Open
Standards
CE, UL recognized E60616 CCN XCFR2, CSA file 70361 class 6228 01
For Load Aluminum Wire Size - Maximum
600 kcmil
For Load Copper Wire Size - Maximum
600 kcmil
For Line Copper Wire Size - Minimum
4 AWG
Maximum Voltage
600 V AC/DC
Maximum Current - Aluminum Conductor
340 A
Terminal Material
Aluminum
Maximum Current - Copper Conductor
420 A
Maximum Operating Temperature
302 Degrees F
Load Side Connection Type
Lug
For Line Copper Wire Size - Maximum
600 kcmil
For Load Copper Wire Size - Minimum
4 AWG
For Load Aluminum Wire Size - Minimum
4 AWG
For Line Aluminum Wire Size - Minimum
4 AWG
For Line Aluminum Wire Size - Maximum
600 kcmil
Line Side Connection Type
Lug
For Conductor Material
Aluminum, Copper
Load Side Wire Range
4 AWG - 600 kcmil
Line Side Wire Size Range
4 AWG - 600 kcmil
Amps
Al conductor: 340 A; Cu Conductor: 420 A
Max. Operating Temp.
302°F
Min. Operating Temp.
-40°F
Short Circuit Current Rating
100 kA UL 508 A
Electrical Connection
tin plated aluminium lugs
Wire Strip Length
Line 1.38 in; Load 1.38 in
Height
4.75 in (120.65 mm)
Line Rated Current
420-420 A copper, 340-340 A aluminium
Number of Terminals
1 line, 1 load
Wire Stripping Length
line: 1.38 in, load: 1.38 in
Ambient Air Temperature For Operation
-40-302°F
Product Compatibility
9080LB41
Mounting Support
surface mount
Product or Component Type
Power Distribution Block
Connections - Terminals
line lug 500 lbf.in AWG 4...600 kcmil copper or aluminium, load lug 500 lbf.in AWG 4...600 kcmil copper or aluminium
[Ics] Rated Service Breaking Capacity
100 kA UL 508 A
Number of Cables
line 1 , AWG 4...600 kcmil, copper or aluminium, load 1 , AWG 4...600 kcmil, copper or aluminium
Terminal Tightening Torque
Line lug 500 lbf.in (56.49 N.m) AWG 4 to 600 kcmil copper or aluminium; Load lug 500 lbf.in (56.49 N.m) AWG 4 to 600 kcmil copper or aluminium
Wire Size
Line 1, AWG 4 to 600 kcmil, copper or aluminium; Load 1, AWG 4 to 600 kcmil, copper or aluminium
Terminals Per Pole
1 line; 1 load
Current Rating
420 A copper; 340 A aluminium
Block Material
Phenolic: block
Country of Origin (subject to change)
United States