Item
Power Distribution Block
Voltage Rating
1000V AC/DC
Wire Range
6 AWG to 350MCM, 14 AWG to 4 AWG
Features
All sizes have optional adder poles for increased flexibility and ease-of-use. Adder poles allow for customization of primary and secondary wire combinations.
Fuse UL Class
UL1953 Open-style
Max. Operating Temp.
80 deg C
Hex/Screw Size u0026 Type (Primary)
11/16-16 x .88
Short Circuit Rating (Class CC)
30 kA
Short Circuit Rating (Standalone)
10 kA
Hex/Screw Size u0026 Type (Secondary)
5/16-24 x .38
Connector Material
Tin-plated Aluminum
Number of Openings per Pole (Primary)
2
Short Circuit Rating (Class J)
600 kA
Short Circuit Rating (Class G)
60 kA
Short Circuit Rating (Class RK5)
600 kA
Short Circuit Rating (Class L)
800 kA
APPROVALS u0026 STANDARDS
UL Listed to subject 1953, File E352417 unless noted otherwise; CSA Certified Class 6228 01
Short Circuit Rating (Class RK1)
600 kA
Short Circuit Rating (Class T)
800 kA
Mounting Hole Dia.
0.75 in, 0.27 in
Country of Origin (subject to change)
Mexico