Item
Power Distribution Block
Primary Connections/Pole
2
Primary Wire Range (AWG)
14 to 2/0 AWG, 6 AWG to 350 MCM
Secondary Connection/Pole
8
Secondary Wire Range (AWG)
14 to 8 AWG
Power Distribution Block Design
Finger-Safe
Voltage Rating
1000V AC/DC
Standards
CE Component IEC, CSA Class 6228, IEC-947-7-1, 529, 68-2-6, UL 1059
Length (Straight Wireway)
3.97 in
Load Side Wire Range
14 AWG - 2 AWG
Maximum Current - Aluminum Conductor
310 A
For Line Copper Wire Size - Maximum
350 kcmil
Maximum Current - Copper Conductor
310 A
Line Side Stud Size
Not Applicable
For Load Copper Wire Size - Minimum
14 AWG
Line Side Connection Type
Lug
Maximum Voltage
1,500 V DC
For Line Copper Wire Size - Minimum
14 AWG
For Line Aluminum Wire Size - Maximum
2/0 AWG, 350 kcmil
Load Side Connection Type
Lug
Line Side Wire Size Range
14 AWG - 350 kcmil
For Line Aluminum Wire Size - Minimum
14 AWG
Compatible with Series
FSPDB
For Load Aluminum Wire Size - Minimum
14 AWG
For Load Copper Wire Size - Maximum
2 AWG
Special Features
Captive Termination Screws, Compact Modularity, Snap On DIN-Rail Mounting
Primary Wire Range
14 to 2/0 AWG, 6 AWG to 350 kcmil
Secondary Wire Range
14 to 2 AWG
For Conductor Material
Aluminum
Load Side Stud Size
Not Applicable
For Load Aluminum Wire Size - Maximum
2 AWG
Terminal Material
Aluminum
Mounting
Screw Mount or DIN Rail
Includes
Cap plugs; Circuit identification markers; End anchors
Max. Operating Temp.
80°C
Features
Finger-safe protection; Flammability Rating 94 V-0
Number of Openings per Pole (Primary)
2
Hole Diameter (Secondary)
0.31 in
Short Circuit Rating (Class RK1)
400 kA
Short Circuit Rating (Class G)
60 kA
Short Circuit Rating (Class L)
0 kA
Connector Type (Secondary)
Box
Torque Rating (Primary)
350-3/0 200; 2/0-#1 100; #2-#6 80; #8-#14 35
Short Circuit Rating (Standalone)
10 kA
Connector Type (Primary)
Box
Short Circuit Rating (Class T)
400 kA
Hole Diameter (Primary)
2 in
Wire Range (Secondary)
#2 - #14
APPLICATIONS
Splicing cables; Splitting primary power into a variety of secondary circuits; Providing a fixed junction tap-off point
Number of Openings per Pole (Secondary)
8
Short Circuit Rating (Class RK5)
200 kA
Body/Insulating Material
Nylon
Short Circuit Rating (Class J)
400 kA
Wire Range (Primary)
350 mcm u0026 2/0 - #14
Short Description
FSPDB UL1059 AL 600V 310A 1-pole 2 in/8 out Box/Box
Short Circuit Rating (Class CC)
30 kA
Installation Mounting
Screw Mount or DIN Rail
Item Description (ERP)
FINGER SAFE AL PDB (1)350 KCMI
Connector Material
Tin-plated Aluminum
Rated voltage DC UL
1500 V
Torque Rating (Secondary)
#8-#14 35
APPROVALS u0026 STANDARDS
UL Recognized Component Guide XCFR2, File E73571; CSA Certified: Class 6228, File 69363; IEC-947-7-1, 529, 68-2-6, CE Marked
Country of Origin (subject to change)
Mexico