Item
Safety Interlock Switch
AC Contact Rating
6 A @ 300 V
DC Contact Rating
3 A @ 300 V
Solenoid Voltage
24 V AC/DC
Operating Temp. Range
-13 Degrees to 158 Degrees F
Description/Special Features
Dust Tight and Corrosion Resistant (Indoor/Outdoor) Enclosure, Orange LED - Green LED Pilot Light, Water Tight
Style
Actuating Key, Solenoid Locking
Standards
CSA C22.2 No 14, EN 1088/ISO 14119, EN/IEC 60204-1, EN/IEC 60947-5-1, EN/ISO 12100, UL 508
Actuator Length
Key Dependent
Connection Type
1/2 in NPT Conduit
Electrical Connection
1/2 in NPT Conduit
Features
(2) LED Pilot Lights (Green/Orange)
Vibration Resistance
5 gn 10-500 Hz)IEC 60068-2-6
Shock Resistance
10 gn 11 ms IEC 60068-2-27
Mechanical Durability
1000000 cycles
Head Type
key operated turret head
Manufacturer Warranty Length
18 mo
Actuating Key Type
Pivoting, Flat
Mechanical Operating Durability
1,000,000
NEMA Enclosure Rating
12, 4, 4X
Circuitry Action
Slow Action
Operating Temperature - Maximum
158 Degrees F
Operating Temperature - Minimum
-13 Degrees F
Resistance Properties
Corrosion Resistant, Dust Resistant, Shock Resistant, Vibration Resistant, Watertight
Maximum Operating Rate
10 cyc/mn for maximum durability
Product Or Component Type
safety switch
Maximum Actuation Speed
0.5 m/s
Signalling Circuit Voltage
24/48 V 20...52 V)
Signalling Circuit Consumption
7 mA
[Ithe] Conventional Enclosed Thermal Current
6A
Solenoid Contacts Type And Composition
1 NC + 1 NO slow-break, simultaneous)
Contacts Type And Composition
2 NC + 1 NO
Product Certifications
UL || CSA
Ambient Air Temperature For Operation
-25-40°C
Minimum Actuation Speed
0.01 m/s
Ip Degree Of Protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Signalling Circuit Type
AC/DC
Short-Circuit Protection
10 A cartridge fuse gG (gl)
Power Consumption In Va
10 VA inrush || 10 VA sealed
Safety Level
can reach category 4 with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach PL = e with the appropriate monitoring system and correctly wired EN/ISO 13849-1 || can reach SIL 3 with the appropriate monitoring system and correctly wired EN/IEC 61508
[Ie] Rated Operational Current
0.55 A 125 V, DC-13, Q300 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q300 EN/IEC 60947-5-1 || 3 A 120 V, AC-15, B300 EN/IEC 60947-5-1 || 1.5 A 240 V, AC-15, B300 EN/IEC 60947-5-1
Contact Operation
slow-break, break before make
Ambient Air Temperature For Storage
-40-70°C
Local Signalling
for guard open/guard closed and locked 2 LEDs (green or orange)
[Ui] Rated Insulation Voltage
50 VEN/IEC 60947-1 signalling circuit
Actuator Forcible Withdrawal Rtc
2000 N
Cable Entry
2 entries tapped 1/2
Electromagnet Interlocking
locking on de-energisation and unlocking on energisation of solenoid
Minimum Actuator Force For Extraction
20 N
[Us] Rated Supply Voltage
24 V - 20...10 %
Protection Type
overvoltage protection signalling circuit
Positive Opening
with NC contact
[Uimp] Rated Impulse Withstand Voltage
6 kV EN/IEC 60947-5-1
Electrical Shock Protection Class
class I EN/IEC 61140
Country of Origin (subject to change)
Multiple