Output Voltage
220/230/240V AC
Backup Time (Half/Full Load)
10.8 min/4.3 min
NEMA Plug Configuration
C14
Automatic Volts Regulation
Yes
Green Environmental Attribute
Product Contributes To Reducing Energy Consumption
Includes
(2) C13 to C14 Interconnection Cables, Phone Cable, USB Cable
NEMA Receptacle Configuration
(4) C13
VA Rating - UPS Systems
800.0 VA
Fax/Modem Line Protection
Yes
Special Features
Hot Swappable Batteries
Green Certification or Other Recognition
UL1778cULCE 62040GOSTSASOIRAM
Capacity - Batteries
800 VA/475 W
Battery Type
Valve Regulated Lead Acid (VRLA)
UPS Certifications
Tested to UL1778 (USA); CE; Tested to GOST (Russia); Tested to SASO (Saudi Arabia); Tested to IRAM (Argentina)
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
Battery Mode BTU / Hr. (Full Load)
458
Half Load Runtime (min.)
10.8 min. (240w)
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Communications Cable
USB interface cable included
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
AC Mode Efficiency Rating (100% Load)
0.97
UPS AC Suppression Joule Rating
340
Nominal Input Voltage(s) Supported
230V AC
UPS Power Module Dimensions (hwd, in.)
10.8 x 5.2 x 7.5
Primary UPS Height (mm)
274
Low Voltage Transfer to Battery Power (Setpoint)
159
Output AC Waveform (Battery Mode)
PWM sine wave
Individually Controllable Load Banks
No
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 159
UPS Input Cord Length (ft.)
0.5
Hot-Swap PDU options
PDUBHV10 (2U / 8 C13 outlets)
Battery Replacement Description
Hot-swappable, user replaceable batteries
Installation Form Factors Supported with Optional Accessories
Wallmount ( UPSWM - tower mounting kit)
Included Output Power Cables
Includes 2 C13 to C14 output power cables
Battery Recharge Rate (Included Batteries)
Less than 4.5 hours from 10% to 90%
Primary UPS Depth (mm)
191
Frequency Compatibility
50 / 60 Hz
UPS AC Suppression Response Time
Instantaneous
Internal UPS Replacement Battery Cartridge
RBC51
Undervoltage Correction
Input voltages between 159 and 199 are boosted by 14%
Nominal Output Voltage(s) Supported
220V; 230V; 240V
Full Load Runtime (min.)
4.3 min. (475w)
Output Volt Amp Capacity (VA)
800
UPS Input Connection Description
Attached 15cm line cord with C14 inlet. The C14 accepts a user-supplied AC power cord with country-specific plug.
Installation Form Factors Supported with Included Accessories
Tower
Relative Humidity
0 to 95%, non-condensing
Output Voltage Regulation (Battery Mode)
+/- 5%
EMI / RFI AC Noise Suppression
Yes
Frequency Compatibility Details
Automatic frequency selection
Output Watt Capacity (Watts)
475
UPS Dataline Suppression
1 line TEL/DSL (1 in / 1 out)
Battery Access
Battery access door
DC System Voltage (VDC)
12
Communications Interface
USB
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
PowerAlert Software
For local monitoring via the UPSâ„¢s built-in USB port, download PowerAlert Local software at http://www.tripplite.com/poweralert
Audible Alarm
Audible alarm indicates power-failure and low-battery conditions
Rated input current (Maximum Load)
2.4A
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LED Indicators
4 LEDs indicate line power, battery power, overload and battery low/replace status
High Availability UPS Features
Hot swappable batteries
Backup/Run Time (Half Load)
19 Minute
Load Capacity
800 VA/475 W
Certifications u0026 Standards
UL1778, cUL, CE 62040, GOST, SASO, IRAM
Typical Battery Recharge Time
4 Hour
Package Contents
Omni VS 800 VA Wall-mountable Tower UPS, OMNIVSINT800 line interactive UPS, 2 C13 to C14 interconnection cables, USB and phone line cables, Owner's manual with warranty information
Additional Information
Voltage regulation description: Line interactive voltage regulation corrects brownouts as low as 159V back to usable levels, Direct pass through: Voltages of 199V and greater are passed through to connected equipment unchanged, Brownout correction: Input voltages between 159 and 199 are boosted by 14%, Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 159V or less. Resets back to line power as line voltage increases to 167V or higher, High voltage transfer to battery power: Yes, Cold Start: Yes, inverter can be
Package Includes
OMNIVSINT800 line interactive UPS;2 C13 to C14 interconnection cables;USB and phone line cables;Owner's manual with warranty information
UPS Applications
Home/Office Desktop
Battery Mode Heat Dissipation (BTU/Hr) @ Full Load
458
Product Certifications
GOST (Russia); IRAM (Argentina); UL 1778
Output Capacity (Watts)
475
Product Compliance
SASO (Saudi Arabia); CE (Europe)
Country of Origin (subject to change)
China